I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

SIMATIC S7 HART Analog Modules<br />

The HART output type is set as default. There are other default settings for<br />

substitute values, diagnostics, and interrupts (see Table 4-4). The HART<br />

analog output module uses these settings, unless you modify them using<br />

STEP 7.<br />

Wire break monitoring is possible for the current range 0/4 to 20 mA.<br />

Conditions: A minimum output current of >500A is required.<br />

The HART analog modules support the function “Change modules during<br />

operation.” However, it is only possible to evaluate the insert / remove<br />

module interrupts with a S7/M7 400 CPU master an active backplane bus in<br />

the ET 200M.<br />

Information on operating the modules in a distributed configuration with a<br />

standard master can be found in manual /140/ . The manual lists the<br />

differences to be taken into consideration if you are operating the modules<br />

with a S7/M7 DP master and a standard master (for example IM 308C with<br />

S5).<br />

Parameter assignment with COM PROFIBUS (.GSE file or type file<br />

required)<br />

Restricted evaluation when inserting or removing modules<br />

If the 24 V load voltage falls below the permitted rated range (< 20.4 V),<br />

there may be a reduction in the output current at connected loads > 650 <br />

and output currents > 20 mA before a diagnostic message is transmitted.<br />

The analog outputs can be readback in the user data range (see Fig. 4-20)<br />

with a resolution of 8 bits. (+polarity). Please note that the readback analog<br />

output is only available after a conversion time which varies with the<br />

precision desired.<br />

4-21