3.3.3 Connection of Resistance Thermometers (e.g. Pt 100) and<br />

Resistance Sensors<br />

Lines for analog<br />

signals<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

The resistance thermometers/resistant sensors are measured by means of a<br />

4-wire connection terminal. The resistance thermometers/resistance sensors<br />

are fed a constant current via terminals IC + and IC - . The voltage produced at<br />

the resistance thermometer/resistant sensors is measured via terminals M+<br />

and M- . In this way, a higher degree of accuracy of the measured results at<br />

the 4-wire connection terminal are achieved.<br />

Shielded lines twisted in pairs are used for analog signals. So as to reduce<br />

interference influence .<br />

Use a twisted-pair wire for the constant current line Ic+ and the sensing line<br />

M+ in the 4-wire connection of thermal resistors and a second twisted pair for<br />

Ic+ / M+. You will achieve a further improvement if you also twist these two<br />

twisted-pair wires with each other (star-quad).<br />

The information provided in Section 3.2 on differences in potential UCM and<br />

UISO between the individual circuits still retains its validity.<br />

Fig. 3-10 shows the connection of resistance thermometers to the isolated<br />

analog input module SM 331; AI 8 x TC/4 x RTD.<br />

I C<br />

I C<br />

CH0<br />

CH1<br />

.<br />

.<br />

.<br />

CH6<br />

CH7<br />

M+<br />

M-<br />

I C+<br />

I C-<br />

M+<br />

M-<br />

IC+ IC- ADU<br />

SIMATIC S7 Ex Analog Modules<br />

P5V<br />

M internal<br />

Logic<br />

Backplane<br />

bus<br />

Fig. 3-10 Connection of resistance thermometers to the isolated analog input module<br />

SM 331; AI 8 x TC/4 x RTD<br />

For the 2-wire, 3-wire connection, you must connect corresponding jumpers<br />

in the module between M+ and IC + or M- and IC - . However, accuracy losses<br />

in the measurement results should be expected as voltage drops at the<br />

relevant supply lines cannot be recorded.<br />

3-33