Type designations<br />

for lines in<br />

accordance with<br />

harmonized<br />

standards<br />

Mechanical Configuration of an Automation System with SIMATIC S7 Ex Modules<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

The type designations for lines in accordance with harmonized standards are<br />

listed in the following:<br />

–<br />

1 2 3 4 5 6 7 8 9<br />

Fig. 1-12 Type designations for lines in accordance with harmonized standards<br />

1 Basic type H Harmonized type<br />

A National type<br />

2 Rated voltage 03 300/300 Volt<br />

05 300/500 Volt<br />

07 450/750 Volt<br />

3 Insulating material V PVC<br />

R Rubber<br />

S Silicon rubber<br />

4 Sheath material V PVC<br />

R Rubber<br />

N Cloroprene rubber<br />

J Glass fiber braid<br />

T Fabric braid<br />

5 Special features H Ribbon cable, separable<br />

H2 Ribbon cable, notsepar.<br />

6 Conductor pipe U Solid<br />

R Stranded<br />

K Fine wire (permanently<br />

installed)<br />

F Flexible stranded<br />

H Extra fine<br />

Y Tinsel<br />

7 Number of cores ... Number of cores<br />

8 Protected conductor X Without protective con<br />

ductor<br />

G With protective conduc<br />

tor<br />

9 Conductor cross section ... Specified in mm 2<br />