Analog Input SM 331; AI 8 x TC/4 x RTD<br />

Dimensions and Weight<br />

Dimensions W x H x D (mm) 40 x 125 x 120<br />

Weight approx. 210 g<br />

Module-specific data<br />

Number of inputs<br />

8<br />

Resistance sensor 4<br />

Line length, shielded max. 200 m<br />

Type of protection PTB<br />

(see Appendix A)<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

max. 50 m for<br />

voltage ranges<br />

80 mV<br />

and thermocouples<br />

[EEx ib] <strong>II</strong>C<br />

to EN 50020<br />

Test number Ex-96.D.2108 X<br />

Type of protection FM<br />

(see Appendix B)<br />

Voltages, currents, potentials<br />

CL I, DIV 2,<br />

GP A, B, C, D T4<br />

Bus power supply<br />

Isolation<br />

5 V DC<br />

Between channels and<br />

backplane bus<br />

yes<br />

between channels no<br />

Permissible difference in potential of signals from<br />

hazardous area<br />

between channels and<br />

backplane bus (UISO)<br />

between channels<br />

(UCM)<br />

Insulation tested<br />

Channels with respect to<br />

backplane bus<br />

Current input from backplane<br />

bus<br />

60 V DC<br />

30 V AC<br />

60 V DC<br />

30 V AC<br />

with 1500 V AC<br />

max. 120 mA<br />

Module power loss typical 0.6 W<br />

Permissible difference in potential of signals from<br />

non-hazardous area<br />

between channels and<br />

backplane bus (UISO)<br />

between channels<br />

(UCM)<br />

400 V DC<br />

250 V AC<br />

75 V DC<br />

60 V AC<br />

Safety data<br />

(refer to Certificate of Conformity in Appendix A)<br />

Type of protection to<br />

EN 50020<br />

[EEx ib] <strong>II</strong>C<br />

Maximum values per channel<br />

for thermocouples and thermal<br />

resistors<br />

U0 (no-load output<br />

voltage)<br />

max. 5.9 V<br />

I0 (short-circuit current) max. 28.8 mA<br />

P0 (load power) max. 41.4 mW<br />

L0 (permissible external<br />

inductance)<br />

max. 40 m<br />

C0 (permissible external<br />

capacitance)<br />

max. 60 F<br />

Um (error voltage) max. 60 V DC<br />

30 V AC<br />

Ta (permissible ambient<br />

temperature)<br />

max. 60C<br />

Connection of an active sensor with following<br />

maximum values Ui = 1.2 V<br />

Ii = 20 mA<br />

deviating from above-specified values<br />

L0 (permissible external<br />

inductance)<br />

max. 15 m<br />

C0 (permissible external<br />

capacitance)<br />

Analog value formation<br />

max. 17 F<br />

Measuring principle SIGMA-DELTA<br />

Integration time/conversion<br />

time/resolution (per channel)<br />

configurable<br />

Integration time in ms<br />

Basic conversion time =<br />

3 x integration time +<br />

transient recovery time<br />

optomultiplexer in ms<br />

Additional conversion<br />

time for wire break<br />

recognition in ms<br />

Resolution in bit (incl.<br />

overrange)<br />

Interference voltage<br />

rejection for interference<br />

frequency f1 in Hz<br />

SIMATIC S7 Ex Analog Modules<br />

yes<br />

2.5<br />

7.5<br />

+<br />

2.5<br />

yes<br />

162 /3<br />

50<br />

+<br />

2.5<br />

yes<br />

20<br />

60<br />

+<br />

2.5<br />

yes<br />

100<br />

300<br />

+<br />

2.5<br />

2.5 2.5 2.5 2.5<br />

9+<br />

sign<br />

12+<br />

sign<br />

12+<br />

sign<br />

15+<br />

sign<br />

400 60 50 10<br />

3-59