Parameterization<br />
Default settings<br />
Channel groups<br />
Selectable<br />
measurement<br />
mode<br />
Measuring ranges<br />
for 2-wire and<br />
4-wire transducers<br />
I/O Modules with Intrinsically-Safe Signals<br />
C79000-G7076-C152-04<br />
The functions of the analog input module SM 331; AI 4 x 0/4...20 mA are set<br />
with STEP 7 (refer to /231/)<br />
in the user program with SFCs (refer to /235/).<br />
The analog input module features default settings for integration time,<br />
diagnostic interrupts etc. (see Table 3-21). These default settings are valid if<br />
re-parameterization has not been carried out via STEP 7.<br />
The channel group is allocated to each input channel for parameterization of<br />
the analog input module SM 331; AI 4 x 0/4...20 mA. Advantage: You can<br />
specific separate parameters for each channel. Table 3-35 shows the allocation<br />
of channels to channel groups of the analog input module SM 331;<br />
AI 4 x 0/4...20 mA:<br />
Table 3-35 Allocation of analog input channels of the SM 331;<br />
AI 4 x 0/4...20 mA to channel groups<br />
Channel Allocated channel group<br />
Channel 0 Channel group 0<br />
Channel 1 Channel group 1<br />
Channel 2 Channel group 2<br />
Channel 3 Channel group 3<br />
The measurement mode is set with STEP 7 (see Section 3.6.3). The<br />
following types of measurement can be set:<br />
Current measurement<br />
Channel deactivated<br />
Table 3-36 contains all measuring ranges for current measurement with<br />
2-wire and 4-wire transducers. You can set the required measuring ranges<br />
with STEP 7 (see Section 3.6.3).<br />
Table 3-36 Measuring ranges for 2-wire and 4-wire transducers<br />
Selected measurement<br />
mode<br />
Explanation Measuring range<br />
2-wire transducer The digitized analog values are specified in Section 3.1.2 in<br />
Table 3-4 Current measuring range.<br />
4-wire transducer The digitized analog values are specified in Section 3.1.2 in<br />
Table 3-4 Current measuring range.<br />
Wire break check<br />
SIMATIC S7 Ex Analog Modules<br />
from 4 to 20 mA<br />
from 0 to 20 mA<br />
from 4 to 20 mA<br />
Wire break recognition is not possible for the current range 0 to 20 mA.<br />
For the current range from 4 to 20 mA, the input current dropping below<br />
I3.6 mA is interpreted as an wire break and, if enabled, an appropriate<br />
diagnostic interrupt is triggered.<br />
3-65