Parameterization<br />

Default settings<br />

Channel groups<br />

Selectable<br />

measurement<br />

mode<br />

Measuring ranges<br />

for 2-wire and<br />

4-wire transducers<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

The functions of the analog input module SM 331; AI 4 x 0/4...20 mA are set<br />

with STEP 7 (refer to /231/)<br />

in the user program with SFCs (refer to /235/).<br />

The analog input module features default settings for integration time,<br />

diagnostic interrupts etc. (see Table 3-21). These default settings are valid if<br />

re-parameterization has not been carried out via STEP 7.<br />

The channel group is allocated to each input channel for parameterization of<br />

the analog input module SM 331; AI 4 x 0/4...20 mA. Advantage: You can<br />

specific separate parameters for each channel. Table 3-35 shows the allocation<br />

of channels to channel groups of the analog input module SM 331;<br />

AI 4 x 0/4...20 mA:<br />

Table 3-35 Allocation of analog input channels of the SM 331;<br />

AI 4 x 0/4...20 mA to channel groups<br />

Channel Allocated channel group<br />

Channel 0 Channel group 0<br />

Channel 1 Channel group 1<br />

Channel 2 Channel group 2<br />

Channel 3 Channel group 3<br />

The measurement mode is set with STEP 7 (see Section 3.6.3). The<br />

following types of measurement can be set:<br />

Current measurement<br />

Channel deactivated<br />

Table 3-36 contains all measuring ranges for current measurement with<br />

2-wire and 4-wire transducers. You can set the required measuring ranges<br />

with STEP 7 (see Section 3.6.3).<br />

Table 3-36 Measuring ranges for 2-wire and 4-wire transducers<br />

Selected measurement<br />

mode<br />

Explanation Measuring range<br />

2-wire transducer The digitized analog values are specified in Section 3.1.2 in<br />

Table 3-4 Current measuring range.<br />

4-wire transducer The digitized analog values are specified in Section 3.1.2 in<br />

Table 3-4 Current measuring range.<br />

Wire break check<br />

SIMATIC S7 Ex Analog Modules<br />

from 4 to 20 mA<br />

from 0 to 20 mA<br />

from 4 to 20 mA<br />

Wire break recognition is not possible for the current range 0 to 20 mA.<br />

For the current range from 4 to 20 mA, the input current dropping below<br />

I3.6 mA is interpreted as an wire break and, if enabled, an appropriate<br />

diagnostic interrupt is triggered.<br />

3-65