22.07.2013 Views

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

II - DCE FEL ČVUT v Praze

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Digital input SM 321; DI 4 x NAMUR<br />

Dimensions and Weight<br />

Dimensions<br />

W x H x D (mm)<br />

40 x 125 x 120<br />

Weight approx. 230 g<br />

Module-specific data<br />

Number of inputs 4<br />

Line length, shielded max. 200 m<br />

Type of protection PTB<br />

(see Appendix A)<br />

[EEx ib] <strong>II</strong>C<br />

acc. to EN 50020<br />

Test number Ex-96.D.2094 X<br />

Type of protection FM<br />

(see Appendix B)<br />

Voltages, currents, potentials<br />

Bus power supply<br />

Rated load voltage L+<br />

Reverse voltage<br />

protection<br />

Number of inputs which<br />

can be activated<br />

simultaneously<br />

CL I, DIV 2,<br />

GP A, B, C, D T4<br />

DC 5 V<br />

24 V DC<br />

yes<br />

Galvanic isolation<br />

Between channels and<br />

backplane bus<br />

yes<br />

Between channels and<br />

load voltage L+<br />

yes<br />

Between channels yes<br />

Between backplane<br />

bus and load voltage<br />

L+<br />

yes<br />

Permissible difference in potential (UISO) of signals<br />

from hazardous area<br />

Between channels and<br />

backplane bus<br />

Between channels and<br />

load voltage L+<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

4<br />

60 V DC<br />

30 V AC<br />

60 V DC<br />

30 V AC<br />

Between channels 60 V DC<br />

30 V AC<br />

Between backplane<br />

bus and load voltage<br />

L+<br />

60 V DC<br />

30 V AC<br />

Voltages, currents, potentials continued<br />

Permissible difference in potential (UISO) for signals<br />

from non-hazardous area<br />

Between channels and<br />

backplane bus<br />

Between channels and<br />

load voltage L+<br />

400 V DC<br />

250 V AC<br />

400 V DC<br />

250 V AC<br />

Between channels 400 V DC<br />

250 V AC<br />

Between backplane<br />

bus and load voltage<br />

L+<br />

Insulation tested<br />

Channels with respect<br />

to backplane bus and<br />

load voltage L+<br />

Channels among each<br />

other<br />

Between load voltage<br />

L+ and backplane bus<br />

Current input<br />

From backplane bus<br />

From load voltage L+<br />

SIMATIC S7 Ex Digital Modules<br />

75 V DC<br />

60 V AC<br />

with 1500 V AC<br />

with 1500 V AC<br />

with 500 V DC<br />

max. 80 mA<br />

max. 50 mA<br />

Module power loss typical 1.1 W<br />

Status, interrupts, diagnostics<br />

Status indication<br />

Inputs green LED per channel<br />

Interrupts<br />

Hardware interrupt configurable<br />

Diagnostic interrupt configurable<br />

Diagnostic functions<br />

Group fault indication red LED (SF)<br />

Channel fault<br />

indication<br />

red LED (F) per channel<br />

Diagnostic functions<br />

readout<br />

possible<br />

Monitoring for<br />

Short-circuit I > 8.5 mA<br />

Wire break I 0.1 mA<br />

2-5