Mechanical Configuration of an Automation System with SIMATIC S7 Ex Modules<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

All system components which can supply electrical energy in any form<br />

whatsoever must fulfill this condition. This includes in particular:<br />

– The power supply module PS307. It fulfills this condition.<br />

– The MPI interface. It fulfills this condition when all users operate with<br />

safety extra-low voltage. SIMATIC automation systems and<br />

programming units fulfill this condition.<br />

– 115/230V modules. Even if they are used in another cell or in another<br />

programmable controller they must feature safety extra-low voltage on<br />

the system side (i.e. towards the backplane bus).<br />

Any other power circuit (24V DC) used in the system must feature safety<br />

functional extra-low voltage. Refer to the corresponding specifications or<br />

consult the manufacturer.<br />

Also bear in mind that sensors and actuators with external power supply may<br />

be connected to I/O modules. Also ensure a safety extra-low voltage is used<br />

in this case. Even in the event of a fault, the process signal of a 24V digital<br />

module must never reach a fault voltage Um > 60V. This also applies to<br />

non-intrinsically safe components.<br />

Note<br />

All voltage sources, e.g. 24V internal load voltage supplies, 24V external<br />

load voltage supplies, 5V bus voltage, must be electrically interconnected<br />

such that no voltage additions to the individual voltage sources can occur<br />

even under conditions with differences in potential thus ensuring the fault<br />

voltage Um cannot be exceeded You can achieve this, for example, by<br />

referring all voltage sources in the system to the functional ground. Also<br />

refer to the instructions provided in the relevant manuals (see Foreword) for<br />

this purpose. The maximum possible fault voltage Um in the system is 60V.<br />

A minimum thread measure of 50 mm must be maintained between<br />

connection terminals with safety functional extra-low voltage and<br />

intrinsically safe connections.In the process connector this is achieved by the<br />

use of a line chamber (refer to Section 1.2).<br />

It is possible that the specified thread measure cannot be maintained in<br />

individual module components. In this case, you must use the spacer module<br />

DM 370 (refer to Section 1.3) which you must set such that it does not take<br />

up an address range. If you use the ET 200M Distributed I/O, you should<br />

read Section 1.5.<br />

Also take care with regard to the wiring to ensure this specified spacing is<br />

maintained between intrinsically safe and non-intrinsically safe terminals.<br />

1-3