Table 1-8 Working on systems to type of protection: EEx de [ib] T5 .. T6, continued<br />

Type of<br />

protection of<br />

apparatus used in<br />

system<br />

Mechanical Configuration of an Automation System with SIMATIC S7 Ex Modules<br />

Type of work to<br />

be carried out<br />

EEx d Zone 1 Zone 2<br />

Opening the<br />

housing, Ex d<br />

housing only<br />

Connecting/<br />

disconnecting<br />

lines<br />

Current, voltage<br />

and resistance<br />

measurement<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04<br />

Work within Additional<br />

requirements and<br />

notes<br />

Prohibited Allowed if no risk<br />

of explosion<br />

Not allowed<br />

unless in<br />

de-energized state<br />

Allowed if no risk<br />

of explosion<br />

Work not possible Allowed if no risk<br />

of explosion<br />

Soldering Prohibited Allowed in<br />

de-energized state<br />

if soldering<br />

temperature lower<br />

than ignition<br />

temperature<br />

Apparatus in<br />

flameproof<br />

enclosure are no<br />

longer protected<br />

against explosion<br />

if housing is<br />

opened<br />

See also “S7-300, M7-300, ET 200M Automation Systems Principles of<br />

Intrinsically-Safe Design“ Manual, Chapter”Installation, Operation and<br />

Maintenance of Electrical Systems in Hazardous Areas”, Table “Information<br />

for work to be carried out on explosion-protected apparatus” .<br />