SIMATIC S7 Ex Analog Modules<br />

Interrupts, Diagnostics<br />

Interrupts<br />

Limit interrupt Configurable<br />

channels 0 and 2<br />

Diagnostic interrupt configurable<br />

Diagnostic functions configurable<br />

Group fault indication red LED (SF)<br />

Channel fault indication red LED (F)<br />

per channel<br />

Diagnostic information<br />

readout<br />

possible<br />

Data for sensor selection<br />

Input ranges (rated values) /<br />

input resistance<br />

Voltage 25 mV<br />

50 mV<br />

80 mV<br />

250 mV<br />

500 mV<br />

1 V<br />

Resistance 150 Ω<br />

300 Ω<br />

600 Ω<br />

Thermocouples Type:<br />

T, U, E, J, L,<br />

K, N, R, S, B<br />

Resistance thermometer Pt 100,<br />

Pt 200,<br />

Ni 100<br />

Measuring current for thermal<br />

resistors and wire break<br />

testing<br />

Permissible input voltage for<br />

voltage input (destruction<br />

limit)<br />

3-62<br />

approx.<br />

0.5 mA<br />

/10 MΩ<br />

/10 MΩ<br />

/10 MΩ<br />

/10 MΩ<br />

/10 MΩ<br />

/10 MΩ<br />

/10 ΜΩ<br />

/10 ΜΩ<br />

/10 ΜΩ<br />

/10 ΜΩ<br />

/10 ΜΩ<br />

max. 35 V permanent;<br />

75 V for max. 1 s<br />

(pulse duty factor 1:10)<br />

Signal generator connection<br />

for voltage measurement possible<br />

for resistance<br />

measurement with 4-wire<br />

connection with 3-wire<br />

connection1) with 2-wire<br />

connection 1)<br />

possible<br />

Characteristic linearization configurable<br />

for thermocouples Type: T, U, E, J, L, K,<br />

N, R, S, B<br />

for thermal resistors Pt 100, Pt 200, Ni 100<br />

(standard and climatic<br />

range)<br />

Data for sensor selection, continued<br />

Temperature compensation configurable<br />

Internal temperature<br />

compensation<br />

possible<br />

External temperature<br />

compensation with<br />

compensation box<br />

possible<br />

External temperature<br />

compensation with<br />

thermal resistors (e.g.<br />

Pt100)<br />

possible<br />

Compensation for 0 C<br />

reference junction<br />

temperature<br />

possible<br />

Compensation for 50 C<br />

reference junction<br />

temperature<br />

possible<br />

1) Without line resistance correction<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04