SIMATIC S7 Ex Analog Modules<br />

Measuring ranges<br />

for resistance<br />

measurement<br />

3-58<br />

Table 3-33 contains all measuring ranges for resistance measurements<br />

Table 3-33 Measuring ranges for resistance measurements<br />

Selected measurement<br />

mode<br />

Resistance<br />

4-wire connection<br />

Connectable<br />

thermocouples<br />

Explanation Measuring range<br />

The digitized analog values are specified in Section 3.1.2 in<br />

Table 3-5 Resistance measuring ranges.<br />

150 ohms<br />

300 ohms<br />

600 ohms<br />

Table 3-34 shows all connectable thermocouples and thermal resistors. The<br />

linearization of characteristic curves is specified for thermocouples in<br />

accordance with DIN IEC 584.<br />

For thermal resistor measurements, linearization of the characteristic curves<br />

is based on DIN 43760 and IEC 751.<br />

Table 3-34 Connectable thermocouples and thermal resistors<br />

Measurement mode Explanation Measuring range<br />

– Linearization and compensation to 0oC Digitized analog values for the specified Type T [Cu-CuNi]<br />

thermocouples are listed in Section 3.1.2 , Type U [Cu-CuNi]<br />

– Linerazation and compensation to 50o p ,<br />

C<br />

Tables 3-10 to 3-12.<br />

(one unit corresponds to 0.1o yp [ ]<br />

– Linearization and compensation<br />

internal comparison<br />

C)<br />

Type E [NiCr-CuNi]<br />

Type J [Fe-CuNi]<br />

Type L [Fe-CuNi]<br />

1)<br />

Type L [Fe-CuNi]<br />

Type K [NiCr-Ni]<br />

Type N [NiCr-SiNiSi]<br />

Type R [Pt13Rh-Pt]<br />

– Linearization and compensation<br />

external comparison2) Type R [Pt13Rh Pt]<br />

Type S [Pt10Rh-Pt]<br />

Type B<br />

[Pt30Rh-Pt6Rh]<br />

Thermal resistance +<br />

linearization 4-wire connection (temperature<br />

measurement)<br />

The digitized analog values for the<br />

specified thermal resistors are listed in<br />

Section 3.1.2, Tables 3-6 to 3-9.<br />

Pt 100, Pt 200, Ni 100<br />

Standard range<br />

Pt 100 , Pt 200, Ni 100<br />

Climatic range<br />

1) – In the case of internal compensation in the module, all 8 channels are available for temperature measurements<br />

also with different types of thermocouples.<br />

– The terminal temperature of the module is provided at a short-circuited input.<br />

This does not apply to thermocouple Type B which is not suitable for measurements in the ambient<br />

temperature range.<br />

2) Following types of compensation are possible with this measurement method:<br />

– Use of compensation box<br />

The compensation box must correspond to the connected type of thermocouple.<br />

Connection to channel 7.<br />

– Use of thermal resistors in climatic range (e.g. Pt 100) for compensation.<br />

The absolute terminal temperature is determined in the climatic range with a thermal resistor (e.g. Pt 100) for<br />

compensation purposes. In this case, the thermocouples to be compensated can be of different types.<br />

Connection to channels 6 and 7<br />

I/O Modules with Intrinsically-Safe Signals<br />

C79000-G7076-C152-04