Analog value formation<br />
Measuring principle SIGMA-DELTA<br />
Integration time/conversion<br />
time/resolution (per channel)<br />
Configurable<br />
Integration time in ms<br />
Basic conversion time,<br />
incl. integration time in<br />
ms (one channel<br />
enabled)<br />
Basic conversion time,<br />
incl. integration time in<br />
ms (two channels<br />
enabled)<br />
Resolution in bit + sign<br />
(incl. overrange)<br />
Interference voltage<br />
suppression for<br />
interference frequency<br />
f1 in Hz<br />
I/O Modules with Intrinsically-Safe Signals<br />
C79000-G7076-C152-04<br />
yes yes<br />
2.5 162 yes yes<br />
/3 20 100<br />
2.5 162 /3 20 100<br />
7.5 50 60 300<br />
10+<br />
sign<br />
Interference suppression, error limits<br />
13+<br />
sign<br />
13+<br />
sign<br />
15+<br />
sign<br />
400 60 50 10<br />
Interference voltage suppression for f = n x (f1 1 %),<br />
(f1 = interference frequency)<br />
Common-mode interference<br />
Channels with respect to<br />
earth terminal of CPU<br />
(UISO < 60 V)<br />
> 130 dB<br />
Series-mode interference<br />
(measured value +<br />
inter-ference must be within<br />
the input range 0 to 22 mA)<br />
> 60 dB<br />
Crosstalk attenuation between<br />
inputs (UISO < 60 V)<br />
> 130 dB<br />
Operational limit (in total temperature range, referred to<br />
input range)<br />
from 0/4 to 20 mA 0.45 %<br />
Basic error limit (operational limit at 25 C, referred to<br />
input range)<br />
from 0/4 to 20 mA 0.1 %<br />
Temperature error (referred to<br />
input range)<br />
Linearity error (referred to input<br />
range)<br />
Repeatability (in steady-state<br />
condition at 25 C, referred to<br />
input range)<br />
0.01%/K<br />
0.01 %<br />
0.05 %<br />
SIMATIC S7 HART Analog Modules<br />
Interference suppression, error limits, continued<br />
Influence of a HART signal modulated onto the input<br />
signal, referred to input range<br />
Error at integration time<br />
2.5 ms 0.25%<br />
162 /3 ms 0.05%<br />
20 ms 0.04%<br />
100 ms 0.02%<br />
Interrupts, diagnostics<br />
Interrupts<br />
Hardware interrupt configurable<br />
channels 0 and 1<br />
Diagnostic interrupt configurable<br />
Diagnostic functions configurable<br />
Group fault indication red LED (SF)<br />
Channel fault indication red LED (F) per<br />
channel<br />
Diagnostic information<br />
readout<br />
possible<br />
HART communication<br />
active and OK<br />
green LED (H)<br />
Data for transducer supply<br />
No-load voltage<br />
< 29.6 V<br />
Output voltage for<br />
transducer and line with<br />
22 mA transducer current<br />
(50 resistor on module<br />
taken into account)<br />
> 15 V<br />
Data for sensor selection<br />
Input ranges (rated values /<br />
input resistance)<br />
Current 0 to 20 mA;<br />
4 to 20 mA:<br />
Permissible input current for<br />
current input (destruction limit)<br />
Signal sensor connection<br />
40 mA<br />
for current measurement<br />
as 2-wire transducer possible<br />
as 4-wire transducer possible<br />
/50 Ω<br />
/50 Ω<br />
4-19