SIMATIC S7 Ex Analog Modules<br />

Temperature range<br />

type R<br />

3-18<br />

Table 3-17 shows the representation of the digitized measured value for the<br />

temperature range, sensor type R.<br />

Table 3-17 Representation of the digitized measured value of an analog input<br />

module (temperature range, type R)<br />

Temperature<br />

range in C<br />

Decimal Hexadecimal Range<br />

> 2019.0 32767 7FFFH Overflow<br />

2019.0<br />

:<br />

1769.1<br />

1769.0<br />

:<br />

:<br />

-50.0<br />

-50.1<br />

:<br />

-170.0<br />

20190<br />

:<br />

17691<br />

17690<br />

:<br />

:<br />

-500<br />

-501<br />

:<br />

-1700<br />

4EDEH<br />

:<br />

451BH<br />

451AH<br />

:<br />

:<br />

FE0CH<br />

FE0BH<br />

:<br />

F95CH<br />

Overrange 1)<br />

Rated range<br />

Underrange 1)<br />

< -170.0 -32768 8000H Underflow<br />

In the case of incorrect wiring (e.g. polarity reversal, open inputs) or a sensor fault in<br />

the negative range (e.g. incorrect type of thermocouple), on dropping below F95CH<br />

the analog input module signals underflow and outputs 8000H.<br />

1) The characteristic of the thermocouple is not defined in the overrange and<br />

underrange. The rise of the characteristic curve is retained on leaving the linearized<br />

rated range. It is not possible to specify the accuracy of these ranges.<br />

I/O Modules with Intrinsically-Safe Signals<br />