SIMATIC S7 Ex Analog Modules<br />

Voltage measuring<br />

ranges<br />

3-4<br />

With these options you must first ensure by way of interrogation that you will<br />

not change the coding for invalid measured values (-32768 / 8000H and<br />

32767 / 7FFFH) or you incorporate it in the filtering process.<br />

Table 3-3 shows the representation of the digitized measured value for the<br />

voltage measuring ranges 25 mV, 50 mV, 80 mV, 250 mV,<br />

500 mV and 1 V.<br />

Table 3-3 Representation of the digitized measured value of an analog input module (voltage measuring ranges)<br />

Measuring range Units Range<br />

25 mV 50 mV 80 mV 250 mV 500 mV 1 V decimal hexadecimal<br />

> 29.397 > 58.794 > 94.071 >293.96 >587.94 >1.1750 32767 7FFFH Overflow<br />

29.397 58.794 94.071 293.96 587.94 1.1750 32511 7EFFH<br />

: : : : : : : : Overrange g<br />

25.001 50.002 80.003 250.02 500.02 1.0001 27649 6C01H<br />

25.000 50.000 80.000 250.00 500.00 1.0000 27648 6C00H<br />

18.750 37.500 60.000 187.50 375.00 0.7500 20736 5100H<br />

: : : : : : : :<br />

- 18.750 - 37.500 - 60.000 - 187.50 - 375.00 - 0.7500 -20736 AF00H<br />

- 25.000 - 50.000 - 80.000 - 250.00 - 500.00 - 1.0000 -27648 9400H<br />

- 25.001 - 50.002 - 80.003 - 250.01 - 500.02 - 1.0001 -27649 93FFH<br />

Rated<br />

range<br />

: : : : : : : : Underrange g<br />

- 29.398 - 58.796 - 94.074 - 293.98 - 587.96 - 1.1750 -32512 8100H<br />