DCA TERMINAL A IMPROVEMENTS (NEAR TERM) 10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 - CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

D. Medium Voltage Cable Identification: In manholes indicate voltage, feeder number and phase<br />

letter on each cable. Inside equipment indicate phase letter on each cable. Install markers on<br />

cables after arc proofing is applied. Attach with cable ties.<br />

E. Low Voltage Conductor Color-Coding: Provide color coding for as follows:<br />

208/120 Volts Phase 480/277 Volts<br />

Black A Yellow<br />

Red B Brown<br />

Blue C Orange<br />

White Neutral Gray<br />

Green Ground Green<br />

F. Use low voltage conductors with color factory-applied the entire length of the conductors<br />

except as follows:<br />

1. The following color-coding methods may be used in lieu of factory color-coded wire for<br />

sizes No. 4 AWG and Larger.<br />

a. Apply colored, pressure-sensitive plastic tape in half lapped turns for a distance of<br />

6 inches from terminal points and in boxes where splices or taps are made. Apply<br />

the last two laps of tape with no tension to prevent possible unwinding.<br />

G. Provide warning, caution, and instruction signs as follows:<br />

1. Install warning, caution, or instruction signs where required by NEC, where indicated, or<br />

where required for safe operation and maintenance of electrical systems. Install engraved<br />

plastic laminated instruction signs where instructions or explanations are needed for<br />

system or equipment operation. Install butyrate signs with metal backing for outdoor<br />

items. Attach signs to outdoor equipment using two-part epoxy cement.<br />

H. Provide equipment/system, circuit/device identification as follows:<br />

1. Provide engraved plastic laminate identification markers on electrical equipment. For<br />

240V systems and below provide white lettering on black background. For 480/277V<br />

systems, use black lettering on yellow background. Text shall match terminology and<br />

numbering specified in the MWAA Design Manual. Apply markers on all of the<br />

following:<br />

a. Panelboards, electrical cabinets, and enclosures.<br />

b. Contactors.<br />

c. Transformers.<br />

d. Disconnect switches.<br />

e. Control equipment.<br />

f. Circuit breakers<br />

I. Circuit Schedules: For panelboards provide typed circuit schedules with identification of items<br />

controlled by each breaker.<br />

IDENTIFICATION FOR ELECTRICAL SYSTEMS 26 05 53- 3