DCA TERMINAL A IMPROVEMENTS (NEAR TERM) 10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 - CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

C. Provide all components, equipment, parts, accessories and associated quantities required for<br />

complete installations and according to the manufacturer’s installation specifications. All<br />

components may not be specified herein.<br />

2.2 COMMUNICATION OUTLETS<br />

A. Outlet modules: Communications Voice and Data outlets shall be provisioned with 8W, 8 Pin<br />

(RJ45) modules. Each outlet shall be labeled and designated voice or data with a color coded icon.<br />

Connector modules shall utilize insulation displacement techniques. Connectors and modules shall<br />

be removable.<br />

B. Pinning of RJ45 connectors and copper patch panels are globally referred to as in compliance with<br />

EIA/TIA 568A throughout the Division 26 specification sections. However the following shall be<br />

observed<br />

1. RJ45 Jacks provided for outlets designated for use by MWAA shall be pinned EIA/TIA<br />

568A. RJ45 Jacks provided for outlets designated for use by the TSA shall be pinned<br />

EIA/TIA 568B. Refer to the telecommunications outlet for outlet usage designation.<br />

C. Refer to the drawings for outlet configurations. Manufacturer is subject to compliance with<br />

requirements, or as acceptable to The Authority based on the requirements outlined in the Airport<br />

Communications System (ACS) Design Manual/.<br />

D. Outlet configurations: Communications Voice and Data outlets shall be provisioned in various<br />

configurations and quantities as indicated in project Drawings and schedules.<br />

1. Surface mount configuration: Communications outlets to be provisioned as surface mount<br />

configurations shall be furnished with outlet module quantities as defined in the project<br />

Drawings and schedules. Coordinate color selection with the COTR.<br />

2. Flush wall mount configuration: Communication outlets to be provisioned as flush mount<br />

shall be furnished with outlet module types and quantities on a single gang face plate as defined<br />

in the project Drawings and schedules.<br />

2.3 HORIZONTAL STATION CABLES – VOICE AND DATA - UNSHIELDED UTP COPPER<br />

A. All horizontal cables provided for installation shall conform to the requirements of the National<br />

Electric code article 760 and labeled CMP-50 as limited combustion plenum cable.<br />

B. All horizontal cables provided for installation shall be certified as Category 6A as defined by the<br />

requirements of EIA / TIA 568C2 Horizontal Cable Requirements and meet or exceed the<br />

following minimum electrical requirements.<br />

1. ANSI / TIA Category: 6A<br />

2. Cable Type 4Pr. UTP<br />

3. Impedance: 100 Ohms at 100 Mhz (nominal)<br />

4. Mutual Capacitance: 6.0 NF / 100m @1 kHz.<br />

5. Operating Voltage: 80 V<br />

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 4