DCA TERMINAL A IMPROVEMENTS (NEAR TERM) 10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 - CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

B. Provide communications systems backboards with a No. 6 copper grounding conductor to the<br />

nearest referenced ground plate.<br />

C. Bond together system neutrals, service equipment enclosures, all non-current carrying metal parts of<br />

electrical equipment, metal raceway systems, grounding conductor in raceways and cables, and<br />

receptacle ground connectors. Exception: IG receptacles shall have the Equipment Grounding<br />

Conductor carried back to the source IG bar and shall not be bonded to the raceway or box at the<br />

receptacle yoke.<br />

1.5 SUBSTITUTIONS<br />

A. Comply with the requirements of Division 01 Section “Product Requirements.”<br />

1.6 QUALITY ASSURANCE<br />

A. Standards of workmanship shall meet or exceed accepted telecommunications systems industry<br />

installation practices.<br />

1.7 SUBMITTALS<br />

A. General: Comply with the requirements of Division 01 Section “Submittals.”<br />

B. Additional submittal procedures are identified in Division 27 Section “Basic Telecommunication<br />

Requirements” and in the individual technical specification.<br />

C. Bonding equipment, including exothermic or removable screw type.<br />

D. Submit all field test reports.<br />

1.8 PROJECT RECORD DOCUMENTS<br />

A. Comply with the requirements of Division 01 Section “Project Record Documents.”<br />

PART 2 - PRODUCTS<br />

2.1 MATERIALS<br />

A. Grounding Connection Accessories.<br />

1. Electrical insulating tape, heat-shrinkable insulating tubing, welding materials, bonding<br />

straps, as recommended by accessories manufacturers for type of service required.<br />

B. Exothermic welded connections are required where grounding conductors by bonding to building<br />

steel.<br />

GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS 27 05 26 - 2