DCA TERMINAL A IMPROVEMENTS (NEAR TERM) 10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 - CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

SECTION 27 05 26 – GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS<br />

PART 1 - GENERAL<br />

1.1 SUMMARY<br />

A. Communication equipment power system grounding.<br />

B. Communication system grounding.<br />

C. Electrical equipment and raceway grounding and bonding.<br />

1.2 RELATED SECTIONS<br />

A. Division 26 – Applicable Electrical Sections.<br />

B. Division 27 – Communications and Electronic Systems Sections.<br />

C. Division 28 – Electronic Safety and Security.<br />

1.3 REFERENCE STANDARDS<br />

A. Comply with the requirements of the reference standards noted herein, except where more stringent<br />

requirements are listed herein or otherwise required by the Contract Documents.<br />

B. NFPA Compliance: NFPA 70 “National Electrical Code (NEC).”<br />

C. UL Compliance: Applicable requirements of UL Standards Nos. 467 “Electrical Grounding and<br />

Bonding Equipment,” and 869, “Electrical Service Equipment,” pertaining to grounding and<br />

bonding of systems, circuits and equipment. In addition, require compliance with UL Std. 486A,<br />

“Wire Connectors.” Grounding and bonding products are to be UL listed and labeled for their<br />

intended usage.<br />

D. IEEE Compliance: Applicable requirements and recommended installation practices of IEEE<br />

Standards 80, 81, 141 and 142 pertaining to grounding and bonding of systems, circuits and<br />

equipment.<br />

1.4 SYSTEM DESCRIPTION<br />

A. Ground each separately derived electrical source, including transformers, UPS’s and PDU<br />

associated with the Division 27 and 28 sections with a system neutral per the Drawings and as<br />

required by the NEC. Refer to the electrical specifications. Where applicable, building steel shall be<br />

included in the bonding, per the Drawings.<br />

GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS 27 05 26 - 1