DCA TERMINAL A IMPROVEMENTS (NEAR TERM)10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 -CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

2.5 ELECTRICAL COMPONENTS<br />

A. General:<br />

1. Materials shall be of the quality specified herein, new, free from defects, of the best<br />

commercial/industrial grade, and approved by a nationally recognized testing laboratory<br />

wherever published standards exist. Each type of material shall be of the same make and<br />

manufacturer throughout the project. Materials shall comply with NEC or Local Code<br />

requirements, whichever are more stringent.<br />

2. The electrical equipment identified herein is based on products by different<br />

manufacturers and indicates the level of quality and performance required for the<br />

equipment. Provided that the equipment is equal in quality and performance to that<br />

identified herein and meets the requirements of these contract documents, electrical<br />

equipment by Allen-Bradley, Schneider Electric, Cutler-Hammer, Square D, or as<br />

acceptable to The Authority is acceptable for use in this Work.<br />

3. All computers, PLCs, and other components with processor chips shall be “Year 2000”<br />

and “New Daylight Saving Time” compliant. Refer to Warranty section identified herein<br />

for design failure requirements.<br />

B. Motor Control Panels (MCP):<br />

1. Panels shall be designed and arranged by a control company with a history of 5 years<br />

experience of previous work in BHS. Control panels shall be provided fully designed<br />

and manufactured ready to install for field connected wiring. BHSC shall install panels<br />

secured to floor to withstand earthquake conditions of 1.5 times panel force. Provide<br />

fluorescent light fixture(s) inside each motor control panel to properly light electrical<br />

equipment and tagging, which shall turn on when MCP door is opened.<br />

2. Control Device Identification: MCP component identification shall be provided so that<br />

all relays, timers, starters, overloads, fuses, etc. can be readily identified when the MCP<br />

door is opened. In addition to all prime manufacturers' nameplates, all electrical and<br />

mechanical control items mounted in or on panels or pushbutton stations shall be further<br />

identified in the system by permanently attached corrosion-proof, etched, engraved, or<br />

stamped identification plates. Dymo-type labels are not acceptable.<br />

3. All motor control panels and surface-mounted enclosures shall be NEMA Type 12,<br />

except those exposed to direct rain, which shall be Type 3 or 4 Weatherproof. MCP shall<br />

be Hoffman Heavy-Duty Free-Standing Enclosure or as acceptable to The Authority.<br />

Other panels shall be Hoffman or as acceptable to The Authority.<br />

4. Main Power Shutoff: Shall be a heavy duty, 480-Volts, 3 Phase, fused switch. Shutoff<br />

shall be General Electric, Allen-Bradley, Square D or as acceptable to The Authority.<br />

Fuses shall be up to 600A - RK1 fuses. Shutoff shall be installed inside housing with<br />

operating handle arranged for connect or disconnect with doors of control panel in closed<br />

position. Size for added 30% code motor load. The BHSC shall install all required<br />

warning placards on all MCPs.<br />

5. Emergency Power Fusible Disconnect Switch and Operating Mechanism: Shall be a<br />

heavy duty, 480 Volts, 3 Phase, fused. Disconnect shall be General Electric, Allen<br />

Bradley, Square D or as acceptable to The Authority. Fuses shall be RK1 fuses.<br />

Disconnect shall be installed inside the MCP. Size for added 30% code motor load. The<br />

BHSC shall install all required warning placards on all MCPs.<br />

BAGGAGE HANDLING EQUIPMENT 34 77 16 - 44