DCA TERMINAL A IMPROVEMENTS (NEAR TERM)10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 -CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

4. Control stations shall be a single or multiple pushbutton station with labels for each<br />

pushbutton operation. Enclosure shall be a NEMA Type 4/13 pushbutton station,<br />

Allen-Bradley 800T Die Cast Enclosure or as acceptable to The Authority. All control<br />

stations other than START and E-STOP stations for conveyor sections in public view<br />

shall be located on adjacent conveyor sections out of public view and labeled for the<br />

conveyor section being controlled.<br />

K. Audible Warning System:<br />

1. Warning Horn: Along baggage system as shown on the Baggage System Contract<br />

Drawings, furnish and install warning horns. Horns shall be 120-volts AC, 103 dB at 10'<br />

with adjustable volume. Type shall be Edwards “AdaptaHorn” series 876-N5 or as<br />

acceptable to The Authority.<br />

2. Control Station Buzzer: At each control station with a START pushbutton in public<br />

areas, furnish and install a buzzer in the control station. Buzzer shall be 60/250-volts AC<br />

with 120-volt AC supplied to the unit to provide 55 to 60 dB at 2’. Type shall be Mallory<br />

“Sonalert” series SC250E or as acceptable to The Authority.<br />

L. Warning Lights (Rotating Beacon):<br />

1. System Start-up: Light shall be a rotating, 120VAC or 24VDC, flat-base mounting<br />

fixture with a red lens. Location as indicated on drawings and shall be Federal Signal<br />

#121S, Vitalite, Allen Bradley LED Round Beacon 855 Series or as acceptable to The<br />

Authority.<br />

2. Fault/Jam Detection/Emergency Stop: Light shall be a rotating, 120VAC or 24VDC,<br />

flat-base mounting fixture with an amber lens. Location as indicated on drawings and<br />

shall be Federal Signal #121S, Vitalite, Allen Bradley LED Round Beacon 855 Series or<br />

as acceptable to The Authority.<br />

M. Junction Boxes for Control Wiring: Furnish and install all junction boxes with terminal boards<br />

per NEC.<br />

N. Uninterruptible Power Supply (UPS): Furnish and install at least one UPS to provide a<br />

minimum of 15 minutes of power to PLCs during a power outage, prior to emergency power<br />

activation. Unit shall be type manufactured by Sola, APC, Eaton Powerware, or as acceptable<br />

to The Authority. UPS shall have an easy to replace, hot-swappable battery module.<br />

O. Electrical Power Conditioners: The Contractor shall furnish and install power regulators, as<br />

required, to ensure that the power to the control systems is properly conditioned. Regulators<br />

shall be manufactured by Square D, Sola, Best Power model Ferrups, or as acceptable to The<br />

Authority.<br />

P. Fiber Optic Communications:<br />

1. Optic Communications Modules: Converter modules shall be compatible with the data<br />

link communication protocol selected by the BHS designer/integrator for<br />

communications between PLCs and converter modules, and fiber optic cabling type.<br />

Data link communication protocol shall be either TCP/IP Ethernet, data communications<br />

provided by PLC manufacturer, or other protocol acceptable to The Authority. Module<br />

type shall be as manufactured by Phoenix Digital Corporation, Weed Instrument<br />

BAGGAGE HANDLING EQUIPMENT 34 77 16 - 51