DCA TERMINAL A IMPROVEMENTS (NEAR TERM) 10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 - CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

8. All horizontal telecommunications cables shall not exceed 295 feet in length from the station<br />

outlets to the horizontal cross-connects within the Communications rooms.<br />

9. Horizontal cables shall not be spliced but must be continuous from the station outlets to the<br />

horizontal cross-connects within Communications rooms.<br />

10. Terminate all horizontal telecommunications cables according to the TIA/EIA T568A wiring<br />

scheme.<br />

11. The Category 6 connecting hardware used shall be installed to provide minimal signal<br />

impairment by preserving wire pair twists as closely as possible to the point of mechanical<br />

termination. The amount of untwisting in a pair as a result of termination to connecting<br />

hardware shall be no greater than 0.5 inches.<br />

12. Terminate horizontal voice copper cables onto wall-mounted 110-wiring blocks and<br />

horizontal data copper cables onto rack-mounted RJ45 patch panels within the<br />

Communications rooms.<br />

C. Grounding: Contractor shall install grounding as specified in Division 27 Section “Grounding and<br />

Bonding for Communications Systems.”<br />

D. Fire And Smoke Partition Penetrations:<br />

1. Conduit sleeves have been provided as a means of routing cables between various<br />

equipment rooms and into the cable tray in the ceiling space. Openings in sleeves and<br />

conduits used for the PWDS system cables shall be sealed with an approved fireproof,<br />

removable material.<br />

2. Additional penetrations through rated assemblies necessary for passage of PWDS wiring<br />

shall be made using an approved method and permanently sealed after installation of cables.<br />

3.3 LABELING<br />

A. Provide labeling as specified in Division 27 Section “Premise Wiring Distribution System.”<br />

3.4 TESTING<br />

A. Provide testing and submit test reports as specified in Division 27 Section “Premise Wiring<br />

Distribution System.”<br />

B. Test 100 percent of all telecommunications cables installed and submit test reports for all tests.<br />

PART 4 - CONTRACTOR’S QUALITY CONTROL REQUIREMENTS<br />

4.1 GENERAL<br />

A. Comply with applicable provisions of Division 01 Section “Quality Requirements” for<br />

requirements for Contractor Quality Control Program.<br />

END OF SECTION 27 15 00<br />

COMMUNICATIONS HORIZONTAL CABLING 27 15 00 - 8