DCA TERMINAL A IMPROVEMENTS (NEAR TERM)10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 -CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

b) When one or more E-Stop buttons are depressed, the conveyor within<br />

this associated E-Stop zone shall be stopped and the associated<br />

upstream conveyors shall cascade stop. When the E-Stop pushbutton<br />

is depressed, the red light shall flash on the actuated E-Stop<br />

pushbutton and all E-Stop pushbuttons in the E-Stop zone shall be<br />

illuminated solid. After clearing the emergency, the system shall be<br />

restarted by resetting the actuated E-Stop pushbutton and then<br />

pressing the START/RESTART pushbutton. Resetting the E-Stop<br />

pushbutton shall extinguish the lamp of E-Stop pushbutton. The startup<br />

warning system shall activate as required prior to the system<br />

restarting, as described herein.<br />

6) Line Terminus Lateral Stop (Fire Emergency):<br />

a) In the event of a fire, a signal shall be sent to the BHS from the Fire<br />

Alarm System; the PLC programming shall stop all BHS equipment<br />

of the associated Life-Safety zone. The BHS Contractor shall<br />

coordinate interface requirements with the Fire Alarm System<br />

Contractor and installer.<br />

b) System restart shall be accomplished through the system start-up<br />

procedure.<br />

7) Line Terminus Lateral Stop (Power Outage):<br />

a) In the event of a power outage, all fire/security doors shall fully close<br />

after emergency power is provided<br />

2.2 RECIRCULATING MAKE-UP DEVICES<br />

A. Slope Plate Carousel: Not Used.<br />

2.3 SILDER BED BELT CONVEYORS<br />

A. Description: Steel frame slider bed conveyors for normal and high speed operations.<br />

B. Drives: See electrical section for other requirements.<br />

1. Motors:<br />

a. The conveyors shall be driven by AC motors or brake motors that comply<br />

electrically with NEMA MG1. Motors shall be sized for maximum load and belt<br />

speed requirements under continuous operation (minimum size 2 HP), and shall be<br />

capable of withstanding shock caused by frequent starting and stopping under full<br />

load where applicable. If overrun is critical to system control operation, motors<br />

shall be equipped with automatically applied brakes to prevent overrun after the<br />

motors have been de-energized. All motors shall be provided with overload<br />

protection of each leg in the control panel. Bolts for mounting of motors shall be<br />

welded to motor mount frame for easy replacement of motors.<br />

BAGGAGE HANDLING EQUIPMENT 34 77 16 - 35