DCA TERMINAL A IMPROVEMENTS (NEAR TERM) 10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 - CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

B. All wiring, including low voltage wiring outside boxes and enclosures, which is not installed in<br />

a raceway or duct bank, shall be installed in electric metallic tubing (EMT) conforming to UL<br />

797. Minimum size shall be 3/4-inch unless otherwise shown. All electrical work shall be as<br />

specified in Division 26 Electrical Sections, and as shown. Grounding shall be installed as<br />

necessary to preclude ground loops, noise, and surges from adversely affecting system<br />

operation.<br />

C. Maintain consistent color-coding for all wiring/cabling in accordance with the approved shop<br />

drawings.<br />

D. Power line surge protection: All equipment connected to alternating current circuits shall be<br />

protected from power line surges.<br />

E. Device wiring and communication circuit surge protection: Copper wire inputs and outputs<br />

shall be protected against surges induced on communication and device wiring.<br />

3.4 CONNECTIONS<br />

A. All connections of stranded wire to screw terminals shall be by insulated spade lugs, crimp<br />

fastened to wire or as specified otherwise.<br />

B. No splicing of cables is permitted for installation of the system.<br />

C. All non-terminal block connections shall be made with mechanical connectors with insulation<br />

equal to conductor insulation and as approved by the COTR.<br />

D. All conductors and cabinets shall be labeled.<br />

E. Wire shall be guided within terminal cabinets by cable supports. All conductors shall be neatly<br />

led to terminations.<br />

3.5 MOUNTING SCREWS<br />

A. Mounting screws for all junction boxes, including pull boxes, and mounting of all devices are to<br />

be of the pinned torx stainless steel type. Size and thread type as required by manufacturer and<br />

back box type.<br />

3.6 HANGERS AND SUPPORTS<br />

A. The Contractor shall supply all equipment supports, hangers, anchors, bases, sleeves and the<br />

sealing of work to adjacent construction.<br />

B. Submit all data in accordance with Part 1 of this specification.<br />

C. Certify that products meet or exceed specified requirements.<br />

D. Verify field measurements prior to fabrication.<br />

VIDEO SURVEILLANCE SYSTEM 28 23 00 - 10