DCA TERMINAL A IMPROVEMENTS (NEAR TERM) 10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 - CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

B. Electronic Time Switches: Electronic, solid-state programmable units with alphanumeric<br />

display; complying with UL 917.<br />

1. Contact Configuration: 12, SPDT, Individually controlled relays.<br />

2. Contact Rating: 20-A ballast load, 120/277-V ac.<br />

3. Program: 8 on-off set points on a 24-hour schedule and an annual holiday schedule that<br />

overrides the weekly operation on holidays.<br />

4. Circuitry: Allow connection of a photoelectric relay as substitute for on-off function of a<br />

program.<br />

5. Astronomic Time: All channels.<br />

6. Battery Backup: For schedules and time clock.<br />

2.2 OUTDOOR PHOTOELECTRIC SWITCHES<br />

A. Manufacturers: Subject to compliance with requirements, or as acceptable to the Authority,<br />

manufacturers offering products that may be incorporated into the Work include, but are not<br />

limited to, the following:<br />

1. Cooper Industries, Inc.<br />

2. Intermatic, Inc.<br />

3. NSi Industries LLC; TORK Products.<br />

4. Tyco Electronics; ALR Brand.<br />

B. Description: Solid state, with DPST dry contacts rated for 1800 VA, to operate connected load,<br />

complying with UL 773.<br />

1. Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for<br />

intended location and application.<br />

2. Light-Level Monitoring Range: 1.5 to 10 fc, with an adjustment for turn-on and turn-off<br />

levels within that range.<br />

3. Time Delay: Thirty-second minimum, to prevent false operation.<br />

4. Lightning Arrester: Air-gap type.<br />

5. Mounting: Twist lock complying with NEMA C136.10, with base.<br />

2.3 LIGHTING CONTACTORS<br />

A. Manufacturers: Subject to compliance with requirements, or as acceptable to the Authority,<br />

manufacturers offering products that may be incorporated into the Work include, but are not<br />

limited to, the following:<br />

1. GE Industrial Systems; Total Lighting Control.<br />

2. Grasslin Controls Corporation; a GE Industrial Systems Company.<br />

3. Hubbell Lighting.<br />

4. Lithonia Lighting; Acuity Lighting Group, Inc.<br />

5. Square D; Schneider Electric.<br />

6. TORK.<br />

LIGHTING CONTROL DEVICES 26 09 23 - 2