lamp of E-Stop pushbutton. The start-up warning system shall<br />

activate as required prior to the system restarting, as described herein.<br />

c) The security/fire door shall close when the system stops due to E-<br />

Stop.<br />

d) When one or more E-Stop pushbuttons are depressed during the<br />

automatic system stop, the security/fire door will continue to close.<br />

e) After E-Stop pushbutton is depressed, it shall immediately stop all<br />

conveyors except the conveyors before and after the security/fire<br />

door, and after the “Door Obstruction” photosensors at the<br />

security/fire doors identify that the doors are clear, the conveyors<br />

before and after the security/fire doors shall stop and the doors shall<br />

fully close. If the “Door Obstruction” photosensor sees a bag which<br />

is under the door, the conveyors shall advance the bag until the “Door<br />

Obstruction” photosensor is clear, and then the conveyors shall stop<br />

and the door shall close. If the door is not able to be closed, BHS<br />

shall send a signal to ACS.<br />

6) System Stop (Fire Emergency):<br />

a) Provide wiring to connect BHS to the dry contact(s) interface of the<br />

Fire Alarm System. In the event of a fire, a signal shall be sent to the<br />

BHS from the Fire Alarm System; the PLC programming shall stop<br />

all BHS equipment of the associated Life-Safety zone. The BHSC<br />

shall coordinate interface requirements with the Fire Alarm System<br />

Contractor and installer.<br />

b) After BHS receives the Fire Alarm signal, it shall immediately stop<br />

all conveyors except the conveyors before and after the security/fire<br />

doors, and after the “Door Obstruction” photosensors at the<br />

security/fire doors identify that the doors are clear, the conveyors<br />

before and after the security/fire doors shall stop and the doors shall<br />

fully close. If the “Door Obstruction” photosensor sees a bag which<br />

is under the door, the conveyors shall advance the bag until the “Door<br />

Obstruction” photosensor is clear, and then the conveyors shall stop<br />

and the door shall close.<br />

c) System restart shall be accomplished through the system start-up<br />

procedure.<br />

7) Ticket Counter System Stop (Power Outage):<br />

a) In the event of a power outage, all security/fire doors shall fully close<br />

after emergency power is provided and the “Door Clear”<br />

photosensors at the security/fire doors identify that the doors are<br />

clear. If the “Door Obstruction” photosensor sees a bag which is<br />

under the door, the conveyors shall advance the bag until the “Door<br />

Obstruction” photosensor is clear, and then the conveyors shall stop<br />

and the door shall close. If the door is not able to be closed, BHS<br />

shall send a signal to ACS.<br />

b. Transport System:<br />

BAGGAGE HANDLING EQUIPMENT 34 77 16 - 31