DCA TERMINAL A IMPROVEMENTS (NEAR TERM)10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 -CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

c. Line Terminus Lateral:<br />

clear. If the “Door Obstruction” photosensor sees a bag which is<br />

under the door, the conveyors shall advance the bag until the “Door<br />

Obstruction” photosensor is clear, and then the conveyors shall stop<br />

and the door shall close.<br />

1) Line Terminus Lateral Start: After the load conveyor has been activated and<br />

fire/security doors are fully open, each associated transport conveyor shall<br />

be activated in a sequenced order from the downstream end of the transport<br />

segments of the curbside line, and the visual and audible warning<br />

subsystems shall shut off. The lateral conveyor belt shall not start,<br />

(although the Lateral is energized), until the head end photo-eye has<br />

blocked, and the belt shall advance the length of the bag. The lateral belt<br />

shall stop when the head-end photoeye is no longer blocked. The bag<br />

advance function shall not occur if the lateral is ‘full’ (see below).<br />

2) Line Terminus Lateral Restart: Restarting the system due to stoppage from<br />

emergency stop pushbuttons, or motor overloads shall activate the start-up<br />

warning system sequence prior to the system restarting. Systems shall not<br />

start up under any circumstances without activating the start-up warning<br />

system sequence.<br />

3) Line Terminus Lateral Stop (Auto):<br />

a) Automatic stopping of the curbside system shall be accomplished<br />

through a “last bag” photosensor located at the discharge end of the<br />

input conveyor at the public area. Each time the system is started and<br />

when a bag interrupts the photosensor beam, the timing logic shall be<br />

reset. After a time interval sufficient to ensure that all bags in transit<br />

on the conveyor line have reached their destination, the timing logic<br />

shall time out and the transport conveyor shall stop and the<br />

fire/security door shall close. The fire/security door closing function<br />

shall be on an adjustable timer (0 to 5 minutes) in the programming of<br />

the system.<br />

4) Line Terminus Lateral ‘Full’: A photoeye shall be provided at the discharge<br />

end of the lateral. When this photoeye is blocked the control system shall<br />

no longer advance the lateral belt, and the transport function shall cascade.<br />

The fire / security door (of the TSA space doghouse) shall remain open<br />

while the lateral is ‘full’.<br />

5) Line Terminus Lateral Stop (Emergency):<br />

a) The curbside system may be stopped anytime during the normal<br />

operation by depressing the maintained-contact emergency-stop<br />

(E-STOP) button. E-Stop pushbutton shall be provided in every<br />

control station containing a START/RESTART and/or JAM RESET<br />

pushbutton. Zoning of E-Stop shut down shall be as identified herein.<br />

BAGGAGE HANDLING EQUIPMENT 34 77 16 - 34