DCA TERMINAL A IMPROVEMENTS (NEAR TERM)10 AUGUST 2012<br />

TASK ORDER 03: LOBBY IMPROVEMENTS – PKG 4 -CURBSIDE CHECK-IN<br />

RONALD REAGAN WASHINGTON NATIONAL AIRPORT<br />

PROJECT DT1203<br />

D. Ceiling <strong>Attachment</strong>s:<br />

1. Ceiling attachments shall be designed to avoid the transmission of excessive conveyor<br />

periodic or transitory loads into the structure. (The COTR shall determine the<br />

acceptability of specific conditions.)<br />

2. <strong>Attachment</strong>s to steel beams shall be clamped. <strong>Attachment</strong>s to concrete slabs shall be<br />

with drilled expansion anchors sized for the load with adequate safety factors and not<br />

exceeding 2” in depth. <strong>Attachment</strong>s to concrete beams shall be with drilled expansion<br />

anchors into the sides of beams only and placed a minimum of 6” up from the bottom of<br />

beam. All attachments shall be submitted for approval.<br />

E. Wire and Cable Identifications:<br />

1. Field electric wire and cable shall be color-coded and shall have the wire numbers as<br />

shown on the electrical drawings affixed to both ends of each wire and cable, and every<br />

5’-0” apart throughout the length of each wire and cable. Coding shall be as follows:<br />

2. Power Wiring - Line Side: This code applies to all field power wiring from source to the<br />

line side of the fuse in the Motor Control Panel and the power wire colors shall be<br />

verified on site. The neutral, if applicable, shall terminate at the terminal board.<br />

a. Phase "A" (120/208) Black (277/480) Yellow<br />

b. Phase "B" (120/208) Red (277/480) Brown<br />

c. Phase "C" (120/208) Blue (277/480) Orange<br />

d. Neutral (120/208) White (277/480) Gray<br />

e. Mech. Ground (120/208) Green (277/480) Green<br />

3. Power and Control Wiring - Load Side: The code for field power and control wiring<br />

from the load side of the fuses in the Motor Control Panel to all other devices shall be as<br />

follows:<br />

a. Power As stated above<br />

b. A.C. Control Red<br />

c. D.C. Control Blue<br />

d. Neutral White<br />

e. Mech. Ground Green<br />

4. Communications system wiring: Installation and termination of wiring shall follow<br />

premise wiring and horizontal cabling specifications. Cabling shall be properly labeled,<br />

supported, and terminated per industry standards. Cable routing of shall be neat and<br />

dressed out in appearance with adequate service loops and proper Velcro tie straps where<br />

applicable.<br />

F. Programming: The BHSC or approved representative shall program BHS to function as<br />

specified herein. A print out and CD of the programming shall be provided to The Authority for<br />

their use. Refer to submittal requirements identified herein.<br />

3.3 NEW EQUPMENT DEMONSTRATION<br />

A. Pre-Installation Demonstration and Testing of New Equipment Types:<br />

BAGGAGE HANDLING EQUIPMENT 34 77 16 - 53