03.08.2013 Views

OPERATION MANUAL CompoBus/S

OPERATION MANUAL CompoBus/S

OPERATION MANUAL CompoBus/S

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

CS1W-SRM21 Master Unit for CS-series PLCs Section 4-2<br />

100<br />

The functions of each area are given in the following table.<br />

Word Bit Name Function<br />

+0 00 Output Slave Regis- OUT0 Registers a list of the Output The bits in the Special I/O Unit<br />

01<br />

02<br />

tration Table<br />

OUT1<br />

OUT2<br />

Slaves that are normally operating<br />

in the network. This list is<br />

used for checking the Slaves<br />

Area must be registered to correspond<br />

to the node numbers<br />

actually used by the Slaves.<br />

to to with the Slave registration func- Therefore, for Slaves with 16<br />

13<br />

14<br />

OUT13<br />

OUT14<br />

tion. Bits 00 to 15 correspond<br />

to Slave node numbers 0 to 15.<br />

The Output Slave is registered<br />

points or higher, turn ON the<br />

bits for the other node numbers<br />

too. For example, the two con-<br />

15 OUT15 by turning ON its corresponding<br />

bit.<br />

secutive bits used by a 16-point<br />

Slave or the four consecutive<br />

+1 00<br />

01<br />

02<br />

Input Slave Registration<br />

table<br />

IN0<br />

IN1<br />

IN2<br />

Registers a list of the Input<br />

Slaves that are normally operating<br />

in the network. This list is<br />

used to check the Slaves with<br />

bits used by a 32-point Slave<br />

must be set.<br />

to to the Slave registration function.<br />

13<br />

14<br />

IN13<br />

IN14<br />

Bits 00 to 15 correspond to<br />

Slave node numbers 0 to 15.<br />

The Input Slave is registered by<br />

15 IN15 turning ON its corresponding<br />

bit.<br />

+2 00 to 15 Registered Slave Par- The waiting time between when the Master Unit is started until the Slaves<br />

ticipation Monitoring start to be checked using the Slave registration function. The time is set in<br />

Time<br />

increments of 1 ms as a hexadecimal.<br />

The setting range is 0000 (default is 2000 ms) or 0001 to FFDC (1 to 65500<br />

ms). If the monitoring time lapses and there are still registered Slaves not<br />

joined in the network, a verification error (Slave missing) will occur.<br />

+3 00 to 15 Reserved for system<br />

use.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!