03.08.2013 Views

OPERATION MANUAL CompoBus/S

OPERATION MANUAL CompoBus/S

OPERATION MANUAL CompoBus/S

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

I/O Response Time Characteristics Section 2-5<br />

SRT2-ND08S 4-point input, 4-point output sensor<br />

terminal<br />

1 ms max. 1.5 ms max. 1.0 ms max. 1.5 ms max.<br />

SRT1-OD08S 8-point output sensor terminal --- --- 0.5 ms max. 1.5 ms max.<br />

SRT2-OD08S 8-point output sensor terminal --- --- 0.5 ms max. 1.5 ms max.<br />

SRT2-ID04CL(-1) 4-point input water-resistant terminal<br />

1.5 ms max. 1.5 ms max. --- ---<br />

SRT2-ID08CL(-1) 8-point input water-resistant terminal<br />

1.5 ms max. 1.5 ms max. --- ---<br />

SRT2-OD04CL(-1) 4-point output water-resistant terminal<br />

--- --- 0.5 ms max. 1.5 ms max.<br />

SRT2-OD08CL(-1) 8-point output water-resistant terminal<br />

--- --- 0.5 ms max. 1.5 ms max.<br />

E3X-SRT21 8-point/16-point input Fiber Amplifier<br />

Communications Unit<br />

See below. --- ---<br />

Maximum Input Delay<br />

Time for Fiber Amplifier<br />

Communications Unit<br />

52<br />

Model Specifications Input specifications Output specifications<br />

ON delay time OFF delay<br />

time<br />

ON delay<br />

time (See<br />

note 1.)<br />

Note 1. This is the ON response time for the SRT@-ROC@@<br />

2. This is the OFF response time for the SRT@-ROF@@<br />

OFF delay<br />

time (See<br />

note 2.)<br />

For up to 8 sensors connected:<br />

Maximum ON/OFF data input delay time for unit n = 0.1 × n +1.5 (ms)<br />

For 9 sensors or more connected:<br />

Maximum ON/OFF data input delay time for unit n = 0.2 × n +1.5 (ms)