Analog Output Terminals Section 5-8<br />

The following diagram shows the terminal block for the SRT2-DA02.<br />

Wiring Wire the connector terminals of the Analog Output Terminal as shown below<br />

according to voltage output or current output.<br />

Voltage Output Current Output<br />

Output Range and<br />

Conversion Data<br />

BD L<br />

BD H<br />

BD L BD H<br />

BS –<br />

BD<br />

L<br />

BS +<br />

BD<br />

H<br />

BS<br />

–<br />

<strong>CompoBus</strong>/S<br />

communications <strong>CompoBus</strong>/S<br />

communications<br />

power supply<br />

(including<br />

internal circuit<br />

power supply)<br />

–<br />

+<br />

BS<br />

+<br />

NC<br />

NC V0+ I0+ V1+ I1+<br />

NC NC NC 0– NC 1–<br />

External<br />

device<br />

+<br />

–<br />

– I+<br />

V+ – I+<br />

External<br />

device<br />

The digital values that are input are converted to analog data according to the<br />

output range.<br />

1 to 5 V<br />

Values 0000 to 1770 Hex (0 to 6000) correspond to voltages between 1 and<br />

5 V. The output range is 0.8 to 5.2 V.<br />

Voltage<br />

5.2 V<br />

5 V<br />

1 V<br />

0.8 V<br />

8000 FED4<br />

(–300)<br />

0 V<br />

0000 (0)<br />

1770 189C<br />

(6000) (6300)<br />

7FFF<br />

V+<br />

+<br />

–<br />

Hexadecimal<br />

(decimal)<br />

conversion data<br />