Checking Operations of CS-series and CJ-series Master Units Section 6-3<br />

Status Area Location and<br />

Configuration<br />

366<br />

This status can be read out using a Programming Device (such as the CX-<br />

Programmer) to monitor Slave status.<br />

The location and configuration of the status area is shown in the following<br />

table.<br />

PLC Location of Status Area<br />

CS-series and CJseries<br />

PLCs<br />

First word = 2000 + unit number × 10<br />

Usable Node Number is IN0 to IN7 and OUT0 to OUT7<br />

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bits<br />

First word Output Slave Communications Error Flags<br />

+ 8<br />

Slave 7 0<br />

First word Input Slave Communications Error Flags<br />

+ 9<br />

Slave 7 0<br />

Active Output Slave Flags<br />

Slave 7 0<br />

Active Input Slave Flags<br />

Slave 7 0<br />

Usable Node Number is IN0 to IN15 and OUT0 to OUT15<br />

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bits<br />

First word Output Slave Communications Error Flags<br />

+ 16<br />

Slave 7 0<br />

First word Input Slave Communications Error Flags<br />

+ 17<br />

Slave 7 0<br />

First word Output Slave Communications Error Flags<br />

+ 18<br />

Slave 15 8<br />

First word Input Slave Communications Error Flags<br />

+ 19<br />

Slave 15 8<br />

Active Output Slave Flags<br />

Slave 7 0<br />

Active Input Slave Flags<br />

Slave 7 0<br />

Active Output Slave Flags<br />

Slave 15 8<br />

Active Input Slave Flags<br />

Slave 15 8<br />

Status Flag Functions The status flags have the following functions. These flags are automatically<br />

cleared to 0 when the power is turned ON or the system is restarted.<br />

Active Output Slave Flags<br />

These flags indicate whether the corresponding Output Slaves are active<br />

nodes in the <strong>CompoBus</strong>/S communications.<br />

Flag status Meaning<br />

0 (OFF) The corresponding Slave is not participating in communications.<br />

(OFF if the Slave didn’t participate even one time.)<br />

1 (ON) The corresponding Slave is participating in communications.<br />

(Not changed even if the Slave is withdrawn from communications.)<br />

Active Input Slave Flags<br />

These flags indicate whether the corresponding Input Slaves are active nodes<br />

in the <strong>CompoBus</strong>/S communications.<br />

Flag status Meaning<br />

0 (OFF) The corresponding Slave is not participating in communications.<br />

(OFF if the Slave didn’t participate even one time.)<br />

1 (ON) The corresponding Slave is participating in communications.<br />

(Not changed even if the Slave is withdrawn from communications.)<br />

Output Slave Communications Error Flags<br />

These flags indicate whether a communications error has occurred with the<br />

corresponding Output Slaves.<br />

Flag status Meaning<br />

0 (OFF) Normal communications or the Slave is not participating in communications.<br />

1 (ON) Withdrawn from communications (communications error)<br />

(This flag turns OFF automatically when the Slave rejoins communications.)