Connector Terminals Section 5-2<br />

214<br />

Item Specification<br />

Terminal strength Pulling: As stated below<br />

Communications connector: 100 N<br />

Cable connector: 40 N<br />

MIL Connector: 100 N<br />

Tightening: 0.25 N m (for communications connector)<br />

Node number settings The node number is set on a DIP switch. (Set the node<br />

number before turning ON the Slave.)<br />

Weight Approx. 75 g<br />

Note This is the current consumption when all the maximum simultaneous output<br />

points are ON, excluding the current consumption of external sensors.<br />

Output Specifications<br />

Item VOD08S/VOD08S-1 VOD16ML/VOD16ML-1<br />

Output current 0.3 A max./point 0.3 A max./point (2 A common)<br />

(See note.)<br />

Residual voltage VOD08S/VOD16ML: 1.2 V DC max. (between each input<br />

terminal and G)<br />

VOD08S-1/VOD16ML-1: 1.2 V DC max. (between each input<br />

terminal and V)<br />

Leakage current VOD08S/VOD16ML: 0.1 mA max.<br />

VOD08S-1/VOD16ML-1: 0.1 mA max.<br />

ON delay time 0.5 ms max.<br />

OFF delay time 1.5 ms max.<br />

Insulation method Photocoupler<br />

Number of circuits 8 points/single common circuit 16 points/single common circuit<br />

Note When using the V and G terminals of the MIL connector, make sure that current<br />

does not exceed 1 A at each terminal.