Remote I/O Modules Section 5-3<br />

Communications Mode,<br />

Node Number and Output<br />

HOLD/CLEAR Mode<br />

262<br />

Set the node number with the NC, ADR1 through ADR3, and hold/clear output<br />

setting terminals.<br />

circuitry<br />

Internal<br />

(see note 1.)<br />

BS– or G<br />

(see note 2.)<br />

SW (see note 3.)<br />

Note 1. The DR terminal is not used by the SRT1 Series.<br />

2. The HOLD terminal is not used by the Input Module.<br />

3. Low: The input bit is ON. Hi: The input bit is OFF.<br />

Note The HOLD terminal is not used by the Input Module.<br />

Communications Mode Settings (SRT2 Series Only)<br />

The following communications modes are set with the communications mode<br />

setting terminal (DR) as shown below.<br />

DR Communications<br />

mode<br />

Hi High-speed Communications<br />

Mode<br />

Low Long-distance<br />

Communications<br />

Mode<br />

Communications<br />

distance<br />

Communications<br />

baud rate<br />

Communications mode settings are possible for SRT2-series Slaves only.<br />

SRT1-series Slaves are always in high-speed communications mode.<br />

Note Make sure that the communications mode of the Slave is the same as that of<br />

the Master Unit. If the communications modes are not the same, normal communications<br />

with the Master Unit will not be possible. The operating status of<br />

the Slave can be verified with LED indicators. The COMM terminal corresponds<br />

to the COM indicator and ERR terminal corresponds to the ERR indicator.<br />

Node Number Settings<br />

Set the node number with terminals ADR1 through ADR3, as shown in the following<br />

table.<br />

Node number ADR3<br />

(8)<br />

Note 1. Low: The input bit is ON. Hi: The input bit is OFF.<br />

Communications<br />

cycle time<br />

100 m max. 750 kbps 0.5 or 0.8 ms<br />

500 m max. 93.75 kbps 4.0 or 6.0 ms<br />

ADR2<br />

(4)<br />

ADR1<br />

(2)<br />

0 Hi Hi Hi<br />

2 Hi Hi Low<br />

4 Hi Low Hi<br />

6 Hi Low Low<br />

8 Low Hi Hi<br />

10 Low Hi Low<br />

12 Low Low Hi<br />

14 Low Low Low