CJ1W-SRM21 Master Unit for CJ-series PLCs Section 4-3<br />

4-3-2 Switch Settings<br />

Rotary Switches The rotary switches are used to set the Master Unit’s Special I/O Unit number<br />

as a decimal number.<br />

The range of usable node number settings (set using pin 1 of the DIP switch)<br />

are listed in the following table.<br />

DIP switch<br />

pin 1 (NODE)<br />

Usable node number setting Unit number<br />

setting range<br />

OFF IN0 to IN7 and OUT0 to OUT7<br />

(When using the words for one Special I/O Unit (10<br />

words))<br />

ON IN0 to IN15 and OUT0 to OUT15<br />

(When using the words for two Special I/O Units (20<br />

words))<br />

Any unit number in the ranges above can be set, as long as the same unit<br />

number has not been set on another Special I/O Unit mounted in the PLC. Set<br />

the unit number with a small standard screwdriver; be careful not to damage<br />

the switch.<br />

!Caution Always turn the PLC OFF before changing the unit number setting.<br />

The Master Unit is shipped with the unit number set to 00.<br />

The unit number setting determines which words in the PLC’s Special I/O<br />

Unit Area and DM Area are allocated to the Master Unit. Refer to 4-1-3<br />

I/O Allocations in CS-series, C200HX/C200HG/C200HE-(Z)E, and<br />

C200HS PLCs for details.<br />

When the usable node number setting is set to IN0 to IN15 and OUT0 to<br />

OUT15, the <strong>CompoBus</strong>/S Master Unit is allocated twice as many words in<br />

the PLC’s Special I/O Unit Area (the words for unit number set on the<br />

Master and the next unit number). The Master’s unit number and the next<br />

unit number cannot be used by another Special I/O Unit mounted to the<br />

PLC.<br />

If the same unit number is used for the Master and another Special I/O<br />

Unit, an I/O UNIT OVER error will occur in the PLC and it will not be possible<br />

to start up the <strong>CompoBus</strong>/S System.<br />

DIP Switch The DIP switch is used to set the range of usable node numbers of Slaves, the<br />

communications mode, communications stop mode, and Slave registration<br />

function.<br />

4<br />

3<br />

2<br />

1<br />

ON<br />

MACH<br />

No.<br />

x10 1<br />

Note 1. Always turn the PLC OFF before changing the settings.<br />

2. DIP switch pins 1 to 4 are all set to OFF at the factory.<br />

0 1 2 3 4 5 6 7 8 9<br />

0 1 2 3 4 5 6 7 8 9<br />

0<br />

x10<br />

Slave registration function<br />

Communications stop mode<br />

Communications mode<br />

Usable node numbers<br />

0 to 95<br />

0 to 94<br />

107