C200HW-SRM21-V1 Master Unit for CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS PLCsSection 4-1<br />

4-1-2 Switch Settings<br />

76<br />

Indicators<br />

The following table shows the meaning of the indicators.<br />

Indicator Status Meaning<br />

RUN (green) ON The Unit is operating normally.<br />

OFF Indicates one of the following conditions:<br />

The power is OFF, there is an I/O setting error, the CPU<br />

Unit is in standby status, or there is a unit number setting<br />

error.<br />

SD (yellow) ON Data is being transmitted.<br />

OFF Data is not being transmitted.<br />

RD (yellow) ON Data is being received.<br />

OFF Data is not being received.<br />

ERC (red) ON A Slave has been withdrawn from communications.<br />

(Communications error)<br />

OFF The Slaves are communicating normally.<br />

IN/OUT (red) ON An error has occurred with an Output Slave.<br />

OFF An error has occurred with an Input Slave or all Slaves<br />

are operating normally.<br />

8421 (red) ON/OFF These indicators represent the four-digit binary slave<br />

number of the Slave in which the error occurred.<br />

Rotary Switch The Master Unit’s unit number (Special I/O Unit’s unit number) is set with the<br />

rotary switch on the front of the Unit.<br />

MACHINE<br />

No.<br />

The highest possible unit number depends on the PLC model and the usable<br />

node number setting set with pin 1 of the DIP switch.<br />

CPU Unit Number of usable Master Units Usable node number setting<br />

(with DIP switch)<br />

CS1 16<br />

(allocated words for 1 Special I/O<br />

Unit (i.e., 10 words))<br />

C200HX-CPU3@-(Z)E<br />

/-CPU4@-(Z)E, C200HG-<br />

CPU3@-(Z)E<br />

/-CPU4@-(Z)E, All<br />

C200HE/HS PLCs<br />

C200HX/HG-CPU5@-(Z)E/<br />

CPU6@-(Z)E/CPU8@-(Z)E<br />

8<br />

(allocated words for 2 Special I/O<br />

Units (i.e., 20 words))<br />

10<br />

(allocated words for 1 Special I/O<br />

Unit (i.e., 10 words))<br />

5<br />

(allocated words for 2 Special I/O<br />

Units (i.e., 20 words))<br />

16<br />

(allocated words for 1 Special I/O<br />

Unit (i.e., 10 words))<br />

8<br />

(allocated words for 2 Special I/O<br />

Units (i.e., 20 words))<br />

IN0 to IN7 and OUT0 to OUT7 0 to F<br />

IN0 to IN15 and OUT0 to OUT15 0 to E<br />

IN0 to IN7 and OUT0 to OUT7 0 to 9<br />

IN0 to IN15 and OUT0 to OUT15 0 to 8<br />

Unit number<br />

setting range<br />

IN0 to IN7 and OUT0 to OUT7 0 to 9, A to F<br />

IN0 to IN15 and OUT0 to OUT15 0 to 8, A to E<br />

Any unit number in the ranges above can be set, as long as the same unit<br />

number has not been set on another Special I/O Unit mounted in the PLC. Set<br />

the unit number with a small flat-blade screwdriver, being careful not to damage<br />

the switch.