Checking Operations for CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS Master Units Section 6-2<br />

The following table shows some examples of node number displays.<br />

Situation Indicator status Possible remedy<br />

ERC I/O 8 4 2 1<br />

Communications error in the Input ON OFF ON ON OFF ON Check the communications cable to Input<br />

Slave with node number 13<br />

Slave 13 and the status of the Slave itself.<br />

Communications error in the Output ON ON OFF ON ON OFF Check the communications cable to Output<br />

Slave with node number 6<br />

Slave 6 and the status of the Slave itself.<br />

Communications error in the Input ON OFF OFF OFF OFF OFF Check the communications cable to Input<br />

Slave with node number 0<br />

Slave 0 and the status of the Slave itself.<br />

A communications error occurs in ON OFF OFF OFF ON ON First, check the communications cable to<br />

the Output Slave with node number<br />

Input Slave 3 and the status of the Slave<br />

11 after an error occurs in the Input<br />

itself.<br />

Slave with node number 3.<br />

Once the error in Input Slave 3 is cleared,<br />

the display will show the error in Output<br />

Slave 11 and this error can be cleared.<br />

6-2-2 Checking Status Using Status Information<br />

Status Area Location and<br />

Configuration<br />

When using CS-series, C200HX/C200HG/C200HE-(Z)E, or C200HS Master<br />

Units, information on active Slave status and communications error status is<br />

stored for each Slave in the status area of the PLC’s Special I/O Unit Area.<br />

The location and configuration of the status area is shown in the following<br />

table.<br />

Usable Node Number is IN0 to IN7 and OUT0 to OUT7<br />

Two words are used for flags when the max. number of Slaves setting is 16.<br />

PLC Location of Status Area<br />

CS-series PLCs First word = 2000 + unit number × 10<br />

C200HX/C200HG/ Unit numbers 0 to 9:<br />

C200HE-(Z)E, and First word = 100 + unit number × 10<br />

C200HS PLCs Unit numbers A to F (10 to 15):<br />

First word = 400 + (unit number – 10) × 10<br />

First<br />

word + 8<br />

First<br />

word + 9<br />

Output Slave Communications Error Flags<br />

Slave 7 - - - - - - - - - - - - - - - - - - - - - - - 0<br />

Input Slave Communications Error Flags<br />

Slave 7 - - - - - - - - - - - - - - - - - - - - - - - 0<br />

Usable Node Number is IN0 to IN15 and OUT0 to OUT15<br />

Four words are used for flags when the max. number of Slaves setting is 32.<br />

PLC Location of Special I/O Unit Area<br />

CS-series PLCs First word = 2000 + unit number × 10<br />

C200HX/C200HG/ Unit numbers 0 to 8:<br />

C200HE-(Z)E, and First word = 100 + unit number × 10<br />

C200HS PLCs Unit numbers A to E (10 to 14):<br />

First word = 400 + (unit number – 10) × 10<br />

Bits<br />

Active Output Slave Flags<br />

Slave 7 - - - - - - - - - - - - - - - - - - - - - - - 0<br />

Active Input Slave Flags<br />

Slave 7 - - - - - - - - - - - - - - - - - - - - - - - 0<br />

357