CPM2C-S Series CPM2C-S@@@C (-DRT) Section 4-6<br />

4-6-1 Specifications and Part Names<br />

System Configuration The following diagram shows a system configuration of a CPM2C-S PLC with<br />

DeviceNet Slave functions.<br />

Unit Specifications<br />

Unit Number of inputs Number of outputs Model<br />

With <strong>CompoBus</strong>/S Master functions 6 at 24 V DC 4 NPN transistors CPM2C-S100C<br />

4 PNP transistors CPM2C-S110C<br />

With <strong>CompoBus</strong>/S Master and<br />

4 NPN transistors CPM2C-S100C-DRT<br />

DeviceNet Slave functions<br />

4 PNP transistors CPM2C-S110C-DRT<br />

Master Specifications<br />

DeviceNet Master<br />

CS, C200HX/C200HG/C200HE (-ZE),<br />

and CVM1/CV PLCs<br />

DeviceNet Slave<br />

Remote I/O communications<br />

up to 128 inputs and 128<br />

outputs<br />

DeviceNet transmission path<br />

Remote I/O communications<br />

and mes-<br />

DeviceNet Slave<br />

sagecommunications up to 32 inputs<br />

and 32 outputs<br />

CPM2C-S Series<br />

I/O control, interrupt inputs, high-speed counters,<br />

pulse outputs, pulse sync control, and analog I/O<br />

Expansion Units<br />

<strong>CompoBus</strong>/S transmission path<br />

<strong>CompoBus</strong>/S Slave<br />

Item Specification<br />

Programming method Instruction length<br />

1 address/instruction 1 to 5 words/instruction<br />

Number of instructions Basic instructions: 14<br />

Special instruction: 105 (185 variations)<br />

Execution time Basic instructions: 0.64 s (LD instruction)<br />

Special instructions: 7.8 s (MOV instruction)<br />

Program capacity 4,096 words<br />

Maximum I/O points CPU: 10 points (6 inputs and 4 outputs)<br />

Expansion: 338 points (182 inputs and 156 outputs)<br />

Input bits 160 bits: 00000 to 00915 Bits not used as I/O bits in words can<br />

Output bits 160 bits: 01000 to 01915<br />

be used as work bits<br />

<strong>CompoBus</strong>/S input bits 128 bits: 02000 to 02715 Bits not used as <strong>CompoBus</strong>/S I/O bits<br />

<strong>CompoBus</strong>/S output bits 128 bits: 03000 to 03715<br />

in words can be used as work bits<br />

Work bits 672 bits: 02800 to 02915 (words 028 to 029), 03800 to 04915 (words 038 to<br />

049), and 20000 to 22715 (words 200 to 227)<br />

SR bits 448 bits: 22800 to 25515 (words 228 to 255)<br />

TR bits 8 bits: TR0 to TR7<br />

HR bits 320 bits: HR 0000 to 1915 (words HR 00 to 19)<br />

AR bits 384 bits: AR 0000 to 2315 (words AR 00 to 23)<br />

LR bits 256 bits: LR 0000 to 1515 (words LR 00 to 15)<br />

141