Connector Terminals Section 5-2<br />

Input Specifications<br />

Item Specifications<br />

Input current 6 mA max./point at 24 V DC<br />

3 mA min./point at 17 V DC<br />

ON delay time 1.5 ms max.<br />

OFF delay time 1.5 ms max.<br />

ON voltage MD32MIL: 17 V DC min. (between each input terminal and V)<br />

MD32ML-1: 17 V DC min.(between each input terminal and G)<br />

OFF voltage MD32ML: 5 V DC max. (between each input terminal and V)<br />

MD32M-1: 5 V DC max. (between each input terminal and G)<br />

OFF current 1 mA max.<br />

Insulation method Photocoupler<br />

Max. simultaneous<br />

input points<br />

16 points<br />

Number of circuits 16 points/single common circuit<br />

Output Specifications<br />

Item Specifications<br />

Output current 0.3 max./point (4 A common) (See note.)<br />

Residual voltage MD32ML: 1.2 V max. (0.3 A DC between each output terminal<br />

and G)<br />

MD32ML-1: 1.2 V max. (0.3 A DC between each output terminal<br />

and V)<br />

Leakage current MD32ML: 0.1 mA max.<br />

ON delay time<br />

MD32ML-1: 0.1 mA max.<br />

0.5 ms max.<br />

OFF delay time 1.5 ms max.<br />

Insulation method Photocoupler<br />

Number of circuits 16 points/single common circuit<br />

Note When using the V and G terminals of the MIL connector, make sure that current<br />

does not exceed 1 A at each terminal.<br />

Simultaneous Input Points and Installation Spacing<br />

For Connector Terminals with 16 transistor inputs and 16 transistor outputs,<br />

the ambient operating temperature places a limit on the maximum number of<br />

points that can be turned ON simultaneously.<br />

For example, if Connector Terminals are to be mounted in the direction other<br />

than the following directions at an ambient operating temperature of 55°C with<br />

all the 16 points turned ON simultaneously, the Connector Terminals must not<br />

be mounted closely together.<br />

a. Units mounted upside down<br />

b. Units mounted horizontally with the MIL connectors facing downward<br />

c. Units mounted facing downward<br />

If 16 points of any Unit mounted in the above directions need to be turned ON<br />

simultaneously, the spacing of the Units is limited as shown in the following<br />

247