I/O Response Time Characteristics Section 2-5<br />

Recognition of Slave I/O<br />

Status at Startup<br />

50<br />

Note Add another 15 µs to the values shown in the table when using the<br />

Slave registration function or communications stop mode.<br />

CJ-series Master Units<br />

Usable node number setting<br />

IN0 to IN7 and OUT0 to OUT7 IN0 to IN15 and OUT0 to OUT15<br />

TM-out-max = 130 µs TM-out-max = 140 µs<br />

Note Add another 15 µs to the values shown in the table when using the<br />

Slave registration function or communications stop mode.<br />

When the <strong>CompoBus</strong>/S System is turned ON, the I/O of Slaves connected to<br />

CQM1 Masters may not become effective at the same time as the I/O of<br />

Slaves connected to CS-series, CJ-series, C200HX/C200HG/C200HE-(Z)E,<br />

and C200HS Masters.<br />

CS-series, CJ-series, C200HX/C200HG/C200HE-(Z)E, and C200HS<br />

Masters<br />

The I/O of a Slave connected to a CS-series, CJ-series, C200HX/C200HG/<br />

C200HE-(Z)E, and C200HS Master becomes effective when the Active Node<br />

Flag for the Slave goes ON.<br />

CQM1 Masters<br />

The I/O of a Slave connected to a CQM1 Master becomes effective some time<br />

after the Master’s PLC is turned ON.<br />

In High-speed Communications Mode: (PLC cycle time) +118 ms<br />

In Long-distance Communications Mode: (PLC cycle time) +720 ms.