Checking Operations for CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS Master Units Section 6-2<br />

Common Mistakes The following table shows common connection mistakes and their remedies.<br />

Mistake Remedy<br />

A terminator is not connected. Connect a terminator (connector or terminal-block) at the<br />

end of the cable farthest from the Master.<br />

The terminator is not connected at the end of the cable farthest<br />

from the Master.<br />

The master is not connected at one end of the main line in a<br />

system in which the main line must be distinguished from<br />

the branch lines.<br />

The length of the main line, a branch line, or the total length<br />

of the branch lines of the system in which the main line must<br />

be distinguished from the branch lines is not within specifications.<br />

The total communications cable in the system in which the<br />

main line does not need to be distinguished from the branch<br />

lines is not within specifications.<br />

2-conductor VCTF cable, 4-conductor VCTF cable, and<br />

Special Flat Cable are used together in the same system.<br />

364<br />

Connect the terminator at the end of the cable farthest from<br />

the Master.<br />

Connect the Master at one end of the main line.<br />

Make sure that the lengths of the cables in the system are<br />

within the specifications listed in 2-2-2 Maximum Cable<br />

Length, or change the communications mode to Long-distance<br />

Communications Mode so that the length of the<br />

cables in the system will be within specifications.<br />

Refer to 2-2-2 Maximum Cable Length and change the configuration<br />

so that the length of the total communications<br />

cable length will be within specifications.<br />

Use just one kind of cable in the system.<br />

There is a break in the communications cable. Reconnect or replace the communications cable.<br />

When 4-conductor VCTF cable or Special Flat Cable is<br />

being used, a connector is not attached securely to the<br />

cable.<br />

Make sure that the connectors are crimped correctly on the<br />

cable.<br />

A connector is faulty. Replace the faulty connector.