Remote Terminals Section 5-1<br />

Relay Output Specifications (SRT@-ROC08, SRT@-ROC16)<br />

Item Specification<br />

Applicable relay G6D-1A (one for each output point)<br />

Rated load 3 A at 250 V AC/3 A at 30 V DC (resistive loads)<br />

Rated carry current 3 A<br />

Max. contact voltage 250 V AC/30 V DC<br />

Max. contact current 3 A<br />

Max. switching capacity 730 VA (AC), 90 W (DC)<br />

Min. permissible load 10 mA at 5 V DC<br />

This value fulfills the P reference value of opening/<br />

closing at a rate of 120 times per min.<br />

Electrical life expectancy 100,000 operations min. (3 A at 250 V AC/3 A at 30 V<br />

DC, resistive loads at 1800 operations/hour)<br />

300,000 operations min. (2 A at 250 V AC/2 A at 30 V<br />

DC, resistive loads at 1800 operations/hour)<br />

Mechanical life expectancy 20,000,000 operations min.<br />

(at 18,000 operations/hour)<br />

Power MOS FET Relay Output Specifications (SRT@-ROF08, SRT@-<br />

ROF16)<br />

Item Specification<br />

Applicable relay G3DZ-2R6PL (one for each output point)<br />

Load voltage 3 to 264 V AC/3 to 125 V DC<br />

Load current 100 µA to 0.3 A<br />

Inrush current 6 A max. (10 ms)<br />

Note Refer to the PCB Relays Catalog (X33) for the ratings of the G6D and G3DZ.<br />

Reference Data<br />

These graphs are based on actual measured values sampled from the production<br />

line. Treat the data as reference values because there is some variation<br />

in relay characteristics.<br />

The following graphs show the characteristics for G6D-1A Relays installed in<br />

SRT1-ROC08 and SRT1-ROC16 Relay-mounted Remote Terminals.<br />

Life expectancy (Operations × 100,000)<br />

Life Expectancy Max. Switching Capacity<br />

250 V AC/30 V DC<br />

resistive load<br />

250 V AC/30 V DC<br />

inductive load<br />

(cosφ = 0.4, L/R = 7 ms)<br />

Switching current (A)<br />

Switching current (A)<br />

DC resistive load AC resistive load<br />

DC inductive load AC inductive load<br />

(cosφ = 0.4)<br />

Switching voltage (V)<br />