Checking Operations for CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS Master Units Section 6-2<br />

6-2 Checking Operations for CS-series, C200HX/C200HG/<br />

C200HE-(Z)E, and C200HS Master Units<br />

6-2-1 Indicators<br />

Errors and Troubleshooting<br />

Situation Indicator status Probable cause Possible remedy<br />

RUN ERC SD RD<br />

Normal communications<br />

ON OFF ON ON --- ---<br />

PLC’s power OFF OFF OFF OFF OFF The PLC’s power is OFF. Turn the PLC’s power supply ON.<br />

Not connected to OFF OFF OFF OFF The Master is not completely Mount the Master properly.<br />

Backplane<br />

connected to the Backplane.<br />

CPU Unit standby sta- OFF OFF OFF OFF One of the Special I/O Units is Replace the faulty Unit, which will be<br />

tus<br />

faulty.<br />

indicated by a“$” in the I/O table.<br />

Special I/O Unit error OFF OFF OFF OFF Refreshing between the PLC After correcting the cause, toggle the<br />

and Master Unit is not being Unit’s restart bit in the AR Area.<br />

performed properly.<br />

Replace the Unit if it doesn’t reset<br />

when the restart bit is toggled.<br />

I/O UNIT OVER error OFF OFF OFF OFF The same unit number has Set unique unit numbers.<br />

been set on two or more Special<br />

I/O Units.<br />

If the usable node numbers are<br />

within IN0 to IN15 and OUT0 to<br />

An out-of-range unit number OUT15, 9 or F cannot be set. node<br />

has been set.<br />

numbers A to F cannot be used with<br />

C200HX-CPU3@-(Z)E/ -CPU4@-<br />

(Z)E, C200HG-CPU3@-(Z)E/ -<br />

CPU4@-(Z)E, or C200HS PLCs.<br />

I/O BUS error OFF OFF OFF OFF The I/O bus is not connected Check the I/O connecting cables<br />

correctly. (In CS-series PLCs, between all Racks. Clear the error<br />

an I/O BUS error may have<br />

occurred in another Unit.)<br />

after the connection is fixed.<br />

Slave not connected ON OFF ON OFF No Slaves are connected, or Use a Slave that can communicate<br />

the communications mode of properly, or make the communica-<br />

each Slave does not match tions mode of each Slave match that<br />

that of the Master Unit. of the Master Unit.<br />

Communications error ON ON ON --- An error has occurred with a Check the Communications Error<br />

with a Slave<br />

Slave during communications Flags or indicators and clear the<br />

and it is withdrawn from the cause of the communications error.<br />

system.<br />

See Communications Error Node<br />

Number Indicators below.<br />

Communications Error<br />

Node Number Indicators<br />

(C200HW-SRM21-V1 Only)<br />

356<br />

Note Check the system’s operation with just one Slave connected (one Slave at a<br />

time) if the <strong>CompoBus</strong> system does not operate but the Master’s indicator status<br />

does not match any of those in the table.<br />

When a communications error occurs with a Slave during communications<br />

and the ERC indicator lights, the other indicators will show the node number<br />

of the Slave where the error occurred in binary.<br />

When several communications errors occur simultaneously, the node number<br />

of the Slave with the first recognized communications error will be displayed.<br />

The display will not be changed if another communications error occurs while<br />

a node number is already being displayed. A new node number can be displayed<br />

after the first communications error is cleared.<br />

When a communications error occurs in a 16-point or greater Slave, any of<br />

the node numbers currently used by that Slave may be displayed.