CJ1W-SRM21 Master Unit for CJ-series PLCs Section 4-3<br />

Use the following crimping tools.<br />

Model Manufacturer<br />

UD6 (product code 1204436) Phoenix Contact<br />

or ZA3 Series<br />

PZ1.5 Crimper<br />

Weidmuller<br />

(product code 900599)<br />

Preparing and Connecting Communications Cables<br />

Use the following procedure to connect the communications data/communications<br />

power supply to the connector.<br />

Note 1. Always turn OFF the Master’s power supply and communications power<br />

supply before connecting or disconnecting the communications data/communications<br />

power supply<br />

2. Use a dedicated communications connector.<br />

Screwless Connector<br />

Install the screwless communications connector in the Master Unit and then<br />

prepare as follows:<br />

1,2,3... 1. Remove sufficient (approx. 10 mm) insulation from the signal wires for a<br />

crimp terminal, and twist the exposed wire strands together tightly.<br />

Approx. 10 mm<br />

Note If using VCTF cable, cover the severed end of the insulation with vinyl tape or<br />

heat-shrinking tube.<br />

Apply vinyl tape or heatshrinking<br />

tube<br />

2. After installing the crimp terminal to the stripped end of the signal wires,<br />

apply vinyl tape or heat-shrinking tube. The signal wires of the CJ-series<br />

Master Unit’s communications connector can be connected without using<br />

crimp terminals.<br />

Note Always use the specified crimping tool to install crimp terminals. When a<br />

crimping tool is not used, the terminal cannot be correctly crimped and may<br />

cause the cables to be disconnected.<br />

3. Check the direction of the connector and insert each of the signal wires securely<br />

into the back of the connector holes. (The signal wires are fixed, so<br />

a tool is not required to secure them.)<br />

If crimp terminals are not installed on the signal wires, use a small flat-<br />

111