CPM2C-S Series CPM2C-S@@@C (-DRT) Section 4-6<br />

Name and Function of Parts<br />

Communications Port<br />

Used to connect Programming Devices and other<br />

RS-232C devices. Used both as a peripheral<br />

port and RS-232C port. Connection requires<br />

special cable.<br />

<strong>CompoBus</strong>/S Communications Terminal<br />

Used to connect <strong>CompoBus</strong>/S communications cable.<br />

DeviceNet Communications Terminal (for models<br />

with the model number suffix "DRT" only)<br />

Used to connect DeviceNet communications cable.<br />

DIN Track Mounting Hook<br />

Indicators<br />

The following table shows the meaning of the indicators.<br />

DIP Switch<br />

Used to set the operation of the CPM2C-S.<br />

(See CPM2C-S Operation Manual.)<br />

CPU Indicator Section<br />

Indicates the status of CPM2C-S, status of<br />

communications with Slaves, and status of<br />

built-in I/O. Models with the model number<br />

suffix "DRT" have a DeviceNet indicator.<br />

Rotary Switches (for models with the<br />

model number suffix "DRT" only)<br />

Indicates the node number as a DeviceNet<br />

Slave. (See CPM2C-S Operation Manual.)<br />

I/O Connector<br />

Used to connect I/O (6 inputs and 4<br />

outputs). (See CPM2C-S Operation<br />

Manual.)<br />

Indicator Name Color Status Meaning<br />

PWR Power Green ON Power ON<br />

OFF Power OFF<br />

RUN Run Green ON RUN/MONITOR mode<br />

OFF PROGRAM mode or abnormal stop<br />

ERR/ALM Operating error Red ON Fatal error (operation stops)<br />

Flashing Non-fatal error (operation continues)<br />

OFF Normal<br />

SD Sending data Yellow ON <strong>CompoBus</strong>/S sending data<br />

OFF <strong>CompoBus</strong>/S not sending data<br />

RD Receiving data Yellow ON <strong>CompoBus</strong>/S receiving data<br />

OFF <strong>CompoBus</strong>/S not receiving data<br />

ERC Communications Red ON <strong>CompoBus</strong>/S communications error<br />

error<br />

OFF Other<br />

COMM Port communica- Yellow Flashing Communicating with peripheral port or RS-232C<br />

tions<br />

port<br />

OFF Other<br />

MS (models Module status Green/Red --- Lights or flashes according to the status of the<br />

with model<br />

number suffix<br />

“DRT” only)<br />

DeviceNet node. (See note.)<br />

NS (models with<br />

model number<br />

suffix “DRT”<br />

only)<br />

Network status Green/Red --- ON, flashes, or OFF according to the status of<br />

DeviceNet network. (See note.)<br />

0 to 5 Input Yellow ON Input terminals turned ON (See note.)<br />

OFF Input terminals turned OFF (See note.)<br />

0 to 3 Output Yellow ON Output terminals turned ON (See note.)<br />

OFF Output terminals turned OFF (See note.)<br />

Note Refer to the CPM2C-S Series Operation Manual for details.<br />