Checking Operations for CS-series, C200HX/C200HG/C200HE-(Z)E, and C200HS Master Units Section 6-2<br />

The Master Unit’s<br />

SD indicator is<br />

OFF<br />

The Master Unit’s<br />

RD indicator is<br />

OFF<br />

362<br />

Error Probable cause Possible remedy<br />

The Master Unit’s<br />

ERC indicator is<br />

ON<br />

--- Either reset the Master Unit with the PLC’s Restart Bit or turn<br />

the PLC OFF and then ON again. Replace the Master Unit if<br />

the error recurs.<br />

The communications cable is not connected<br />

to the Master.<br />

A Slave’s number has been set to 8 to<br />

15 even though the usable node<br />

address setting is IN0 to IN7 and<br />

OUT0 to OUT7.<br />

One of the Slaves is not turned ON.<br />

(The Slave’s PWR indicator is OFF.)<br />

There is a problem with the Slaves’<br />

power supply.<br />

The Slaves’ power supply is inadequate.<br />

There is a problem with the communication<br />

cable connection or the cable<br />

itself.<br />

Communications modes of Master<br />

Unit and Slave do not match.<br />

A common system mistake has been<br />

made. (Refer to the table on page 364<br />

for a list of common mistakes.)<br />

Connect the communications cable correctly.<br />

Either change the Input and Output Slave’s node number settings<br />

so that they are 0 to 7 or change the usable node number<br />

setting to IN0 to IN15 and OUT0 to OUT15.<br />

Turn ON the Slave’s power supply.<br />

The Master Unit is faulty. Replace the Master Unit.<br />

Power is not being supplied to the<br />

Slaves.<br />

There is a problem with the Slaves’<br />

power supply.<br />

The Slaves’ power supply is inadequate.<br />

There is a problem with the communication<br />

cable connection or the cable<br />

itself.<br />

There is a non-existent node number<br />

because a Slave’s node number was<br />

changed after communications were<br />

established.<br />

The same node number is used on<br />

two Slaves.<br />

A common system mistake has been<br />

made. (Refer to the table on page 364<br />

for a list of common mistakes.)<br />

Check the power supply cable connections and connect the<br />

cables to the Slaves correctly.<br />

Check the power supply capacity. If it is inadequate, either<br />

change the system configuration or change the power supply<br />

so that sufficient power is provided.<br />

Check the connections and cable. Replace the communications<br />

cable if it is faulty.<br />

Set the communications mode so that it is the same as that of<br />

the Master Unit.<br />

Refer to the table on page 364 for common mistakes and<br />

their remedies.<br />

Turn ON the Slave’s power supply.<br />

Check the power supply cable connections and connect the<br />

cables to the Slaves correctly.<br />

Check the power supply capacity. If it is inadequate, either<br />

change the system configuration or change the power supply<br />

so that sufficient power is provided.<br />

Check the connections and cable. Replace the communications<br />

cable if it is faulty.<br />

Either reset the Master Unit with the PLC’s Restart Bit or turn<br />

the PLC OFF and then ON again.<br />

Change the Slaves’ node number settings to eliminate the<br />

duplication and then turn the Slaves ON again. Either reset<br />

the Master Unit with the PLC’s Restart Bit or turn the PLC<br />

OFF and then ON again.<br />

Refer to the table on page 364 for common mistakes and<br />

their remedies.<br />

A Slave Unit is faulty. Replace the faulty Slave Unit.