System Configuration Section 2-2<br />

30<br />

Communication<br />

mode<br />

Long-distance<br />

Communications<br />

Mode<br />

Cable type Cable length<br />

Main line Branch line Total of branch lines<br />

2-conductor VCTF cable 500 m max. 6 m max. 120 m max.<br />

4-conductor VCTF cable Total length of communications cable: 200 m max.<br />

(with no distinction between main and branch lines)<br />

Flat Total length of communications cable: 200 m max.<br />

(with no distinction between main and branch lines)<br />

Note If the number of connected Slaves does not exceed 16 when using the Highspeed<br />

Communications Mode, the main line length can be up to 100 m and<br />

the total branch line length can be up to 50 m (i.e., the same as for the VCTF<br />

cable). An example is given below.<br />

Refer to the following examples.<br />

Example 1<br />

Special Flat Cable Main line length: 100 m max.<br />

Master<br />

Branch<br />

length:<br />

3 m max.<br />

L 1<br />

Slave (8<br />

outputs)<br />

Slave (8<br />

outputs)<br />

Slave (8 outputs) × 5 Units Slave (8 inputs) × 5 Units Total branch line length: 50 m max.<br />

Special Flat Cable<br />

Master<br />

Branch length:<br />

3 m max.<br />

L 1<br />

L 2 L 5 L 6 L 7 L 10 L 11 L 12 L 13 L 14<br />

Slave (16<br />

outputs)<br />

Slave (8<br />

outputs)<br />

Slave (8<br />

inputs)<br />

No. of Slave<br />

Units<br />

Number of I/O<br />

points<br />

Example 2<br />

No. of Slave<br />

Units<br />

Number of I/O<br />

points<br />

Slave (8<br />

inputs)<br />

Slave (8<br />

inputs)<br />

8-input Slave × 5 Units + 8-output Slave × 5 Units + 16-input Slave<br />

× 2 Units + 16-output Slave × 2 Units = 14 Slave Units<br />

72 inputs and 72 outputs<br />

Slave (16<br />

inputs)<br />

L 2 L 8 L 9 L 10 L 16<br />

Slave (16<br />

outputs)<br />

Slave (16 outputs) × 8 Units<br />

Slave (16<br />

outputs)<br />

Main line length: 100 m max.<br />

Slave (16<br />

inputs)<br />

Slave (16<br />

inputs)<br />

Slave (16 inputs) × 8 Units<br />

Slave (16<br />

outputs)<br />

Slave (16<br />

inputs)<br />

Slave (16<br />

outputs)<br />

Terminator<br />

16-input Slave × 8 Units + 16-output Slave × 8 Units = 16 Slave<br />

Units<br />

128 inputs and 128 outputs<br />

Slave (16<br />

inputs)<br />

Terminator<br />

Total branch line length:<br />

50 m max.<br />

Do not mix 2-conductor VCTF, 4-conductor VCTF, and Special Flat Cables in<br />

the same system.<br />

Refer to the Appendix Standard Models for details on compatible communications<br />

cables.<br />

Note When 4-conductor VCTF or Special Flat Cable is used to supply the Slave’s<br />

communications power, the length of the cable may be limited by current and<br />

voltage drops in the cable and connectors. Refer to 2-3-3 Limitations of Communications<br />

Cable Power Supply on page 35 for details.