Supplying Power to the Slaves Section 2-3<br />

Communications Power<br />

Supply<br />

32<br />

The following table groups the Slaves according to their power supply requirements.<br />

Power supply Slave type Model numbers<br />

Network power<br />

supply<br />

Multiple power<br />

supplies<br />

Local power supply<br />

Sensor Terminals<br />

Fiber Amplifier<br />

Communications<br />

Unit<br />

Analog I/O Terminals<br />

Remote Terminals<br />

with Transistors<br />

Connector Terminals<br />

with Transistors<br />

Water-resistant<br />

Terminals with<br />

Transistors<br />

Sensor Terminals<br />

with Connector<br />

Outputs<br />

Remote Terminals<br />

with Relays<br />

Remote Terminals<br />

with Power<br />

MOS FETs<br />

--- Remote I/O<br />

Modules<br />

--- CPM1A/CPM2A<br />

I/O Link Unit<br />

--- CPM2C I/O Link<br />

Unit<br />

SRT1/SRT2-ID08S<br />

SRT1/SRT2-ND08S<br />

E3X-SRT21<br />

SRT2-AD04<br />

SRT2-DA02<br />

SRT1/SRT2-ID04<br />

SRT1/SRT2-ID04-1<br />

SRT1/SRT2-ID08<br />

SRT1/SRT2-ID08-1<br />

SRT1/SRT2-ID16<br />

SRT1/SRT2-ID16-1<br />

SRT1/SRT2-OD04<br />

SRT1/SRT2-OD04-1<br />

SRT1/SRT2-OD08<br />

SRT1/SRT2-OD08-1<br />

SRT1/SRT2-OD16<br />

SRT1/SRT2-OD16-1<br />

SRT2-VID08S<br />

SRT2-VID08S-1<br />

SRT2-VID16ML<br />

SRT2-VID16ML-1<br />

SRT2-ID32ML<br />

SRT2-ID32ML-1<br />

SRT2-VOD08S<br />

SRT2-VOD08S-1<br />

SRT2-VOD16ML<br />

SRT2-VOD16ML-1<br />

SRT2-ID04CL<br />

SRT2-ID04CL-1<br />

SRT2-ID08CL<br />

SRT2-ID08CL-1<br />

SRT1/SRT2-OD08S<br />

SRT1/SRT2-ROC08<br />

SRT1/SRT2-ROC16<br />

SRT1/SRT2-ROF08<br />

SRT1/SRT2-ROF16<br />

SRT1/SRT2-ID16P<br />

SRT1/SRT2-OD16P<br />

CPM1A-SRT21<br />

CPM2C-SRT21<br />

SRT1/SRT2-ID16T<br />

SRT1/SRT2-ID16T-1<br />

SRT1/SRT2-OD16T<br />

SRT1/SRT2-OD16T-1<br />

SRT1/SRT2-MD16T<br />

SRT1/SRT2-MD16T-1<br />

SRT2-OD32ML<br />

SRT2-OD32ML-1<br />

SRT2-MD32ML<br />

SRT2-MD32ML-1<br />

SRT2-OD04CL<br />

SRT2-OD04CL-1<br />

SRT2-OD08CL<br />

SRT2-OD08CL-1<br />

OMRON’s S82-series Power Supplies are recommended for supplying power<br />

to the Slaves for communications. Select a power supply with a current capacity<br />

greater than the total power consumed by all of the Slaves that will be connected.<br />

Note Be sure to provide a power supply with a current capacity sufficient to handle<br />

the surge current that flows at startup.