Supplying Power to the Slaves Section 2-3<br />

2. If multiple <strong>CompoBus</strong>/S Systems are used, provide a separate communications<br />

power supply for each <strong>CompoBus</strong>/S System to prevent unstable<br />

operation due to unwanted noise paths in the power supplies of the <strong>CompoBus</strong>/S<br />

Systems.<br />

<strong>CompoBus</strong>/S<br />

System 1<br />

<strong>CompoBus</strong>/S<br />

System 2<br />

Master<br />

Master<br />

Communications<br />

power supply (See note.)<br />

Main line<br />

Main line<br />

3. When using CJ-series Master Units, use 6-pin communications connectors<br />

that allow simultaneous connection of communications and power<br />

supply cables. Power can be supplied to the Slaves easily by connecting<br />

the communications power supply to the Master Unit without preparing the<br />

communications cables, as shown in the following diagram.<br />

The BS+ and BS– terminals of the CJ-series Master Unit’s communications<br />

connector are connected internally. (The Master Unit does not use<br />

the BS+ or BS– terminals.)<br />

2-3-3 Limitations of Communications Cable Power Supply<br />

Slave<br />

Check the following points when using 4-conductor VCTF or Special Flat<br />

Cable to supply power to Slaves.<br />

The 4-conductor VCTF or Special Flat Cable’s allowable current<br />

The Extension Connector’s allowable current<br />

(when using an Extension Connector)<br />

The allowable current of the CJ-series Master Unit’s communications connector<br />

(when using CJ-series Master Units)<br />

Cable length limit due to voltage drop<br />

1. 4-conductor VCTF or Special Flat Cable’s Allowable Current<br />

The allowable current through the 4-conductor VCTF or Special Flat Cable<br />

depends on the ambient temperature, as shown in the following tables.<br />

Slave<br />

Slave Slave<br />

Note: Use a separate communications power supply for each line.<br />

Communications<br />

Power<br />

supply<br />

Communications<br />

power supply (See note.)<br />

CJ-series<br />

Master Unit<br />

BS+<br />

BDH<br />

BDL<br />

BS−<br />

BS+<br />

BS−<br />

Power<br />

supply<br />

+<br />

H<br />

L<br />

−<br />

+<br />

−<br />

+<br />

−<br />

Special Flat Cable or<br />

4-conductor VCTF<br />

cable (Wiring Special<br />

Flat Cable is easy as<br />

it is connected to the<br />

communications<br />

connector in the<br />

same order.)<br />