Analog Output Terminals Section 5-8<br />

324<br />

0 to 5 V<br />

Values 0000 to 1770 Hex (0 to 6000) correspond to voltages between 0 and<br />

5 V. The output range is –0.25 to 5.25 V.<br />

8000<br />

Voltage<br />

5.25 V<br />

5 V<br />

0 V<br />

FED4<br />

(–300)<br />

–0.25 V<br />

0000 (0)<br />

1770 189C 7FFF<br />

(6000) (6300)<br />

Hexadecimal<br />

(decimal)<br />

conversion data<br />

0 to 10 V<br />

Values 0000 to 1770 Hex (0 to 6000) correspond to voltages between 0 and<br />

10 V. The output range is –0.5 to 10.5 V.<br />

8000<br />

Voltage<br />

10.5 V<br />

10 V<br />

0 V<br />

FED4<br />

(–300)<br />

–0.5 V<br />

0000 (0)<br />

1770 189C<br />

(6000) (6300)<br />

7FFF<br />

Hexadecimal<br />

(decimal)<br />

conversion data<br />

–10 to 10 V<br />

Values F448 to 0BB8 Hex (–3000 to 3000) correspond to voltages between –<br />

10 and 10 V. The output range is –11 to 11 V.<br />

Negative voltages are specified as 2’s complement (16 bits).<br />

F31C F448<br />

8000 (–3300) (–3000)<br />

Voltage<br />

11 V<br />

10 V<br />

0000 (0)<br />

0 V<br />

–10 V<br />

–11 V<br />

0BB8<br />

(3000)<br />

0CE4<br />

(3300)<br />

7FFF<br />

Hexadecimal<br />

(decimal)<br />

conversion data