Checking Operations of CS-series and CJ-series Master Units Section 6-3<br />

For details on the words used to set the Slave registration function, refer to 4-<br />

3-5 Slave Registration Function and Communications Stop Mode.<br />

Word Bit Name Function<br />

+4 00 Registration Completed<br />

Flag<br />

08 Verification Error Flag:<br />

Slave Missing<br />

09 Verification Error Flag:<br />

Unregistered Slave in Network<br />

10 Communications Stopped<br />

Flag<br />

This flag is turned ON when all registered Slaves have joined the network.<br />

If all the registered Slaves have joined the network within the registered<br />

Slave participation monitoring time this flag will turn ON even if<br />

unregistered Slaves have also joined. The flag will not turn ON, however,<br />

if there are no Slaves set in the Slave registration table. The flag<br />

will remain ON until the power is turned OFF and ON again or the Unit<br />

is restarted.<br />

This flag is turned ON under the following conditions.<br />

Registered Slaves do not join the network within the registered Slave<br />

participation monitoring time. When the Slave that caused the verification<br />

error is joined in the network, the flag will automatically be turned<br />

OFF.<br />

Check which Slave caused the error in the bit for verification error<br />

(Slave missing) in Output Slave (first word + 6) or verification error<br />

(Slave missing) in Input Slave (first word + 7).<br />

This flag is turned ON when an unregistered Slave has joined the network.<br />

The flag will remain ON until the power is turned OFF and ON<br />

again or the Unit is restarted, even if the Slave that caused the verification<br />

error is removed from the network.<br />

Check which Slave caused the error in the bit for Output Slave verification<br />

error (unregistered Slave in network) (first word + 8) or Input Slave<br />

verification error (unregistered Slave in network) (first word + 9).<br />

This flag is turned ON when the Master Unit is set to communications<br />

stop mode and remote I/O communications stop due to a communications<br />

error,.<br />

Once the flag has turned ON, the status remains until the power is<br />

turned OFF and ON again or the Unit is restarted.<br />

Check which Slave caused the error in the bits for communications<br />

stopped node number (bits 00 to 07 of first word + 5) and communications<br />

stopped Slave type (bit 15 of first word + 5).<br />

15 Error Flag This flag is turned ON when any of the bits 08 to 10 are set to1(ON).<br />

The flag is automatically turned OFF when all the bits 08 to 10 are<br />

turned OFF.<br />

+5 00 to 07 Communications Stopped<br />

Node Number<br />

15 Communications Stopped<br />

Slave Type<br />

When the Master Unit is set to communications stop mode and remote<br />

I/O communications stop due to a communications error, the node<br />

number of the Slave that caused the error is stored as a 2-digit hexadecimal<br />

(00 to 0F: 1 to 15).<br />

Check the Slave type (Output or Input) in the word for communications<br />

stopped Slave type (bit 15 of first word + 5).<br />

The node address stored will be held until the power is turned OFF and<br />

ON again or the Unit is restarted.<br />

When the Master Unit is set to communications stop mode and remote<br />

I/O communications stop due to a communications error, the Slave type<br />

of the Slave that caused the error is stored as follows:<br />

0 (OFF): Output Slave<br />

1 (ON): Input Slave<br />

Check which Slave caused the error in the bits for communications<br />

stopped node number (bits 00 to 07 of first word + 5)<br />

When communications have stopped, the bit status is held until the<br />

power is turned OFF and ON again or the Unit is restarted.<br />