Master/Slave Connecting Cables Section 3-4<br />

Assembling the Cable<br />

Connectors<br />

68<br />

Use the following procedure to install the sensor’s cable into the cable connector<br />

that plugs into the Sensor Terminal. The following diagram shows the<br />

two parts of the cable connector: the connector plug and cover.<br />

Connector plug<br />

Cable Connector Model Numbers<br />

There are two models of cable connectors available for different sized cable<br />

wires, as shown in the following table.<br />

Model Marking Compatible cable wire size<br />

(cross-sectional area)<br />

XS8A-0441 XS8-1 0.3 to 0.5 mm 2<br />

XS8A-0442 XS8-2 0.14 to 0.2 mm 2<br />

Make sure that the sensor cable’s wire size is compatible the cable connector<br />

being used. The cable connector’s marking is found on the connector plug, as<br />

shown in the following diagram.<br />

Marking<br />

Sensor Cable Preparation<br />

Sensor cables are usually stripped to semi-strip or strip specifications, but<br />

OMRON cable connectors cannot be attached when the cable is stripped in<br />

these ways.<br />

Semi-stripped Stripped<br />

Cover<br />

To prepare the cable for an OMRON cable connector, cut the tip and strip the<br />

cable insulation but not the wire insulation, as shown in the following diagram.<br />

20 mm min.<br />

Inserting Wires into the Cover<br />

When connecting the Sensor, match the terminal numbers marked on the<br />

connector cover with the colors of the sensor wires as shown in the following<br />

table.<br />

Sensor terminal Sensor type Terminal number<br />

1 2 3 4<br />

SRT2-VID08S 3-wire sensor<br />

Black (white) Brown Blue<br />

(without self-diagnostic out- (Connect to 1 or (red) (black)<br />

put function)<br />

2)<br />

2-wire sensor<br />

Brown (white) --- Blue<br />

(without self-diagnostic out- (Connect to 1 or (black)<br />

put function)<br />

2)